(Optional) Setting Communications Parameters
Setting Access Control Parameters
Parameter |
Description |
---|---|
Remote control |
|
SSH (LAN) |
|
Setting Communications Parameters (Modbus-RTU Protocol)
Procedure
- On the home screen, choose .Figure 6-14 Modbus Settings
- Set the baud rate, communication address, and RS485 monitoring group.
Parameter
Description
Baud rate
Set this parameter based on the baud rate of the connected device. The baud rate must be the same as that on the NMS. The value can be 9600 or 19200.
Communication address
Enter the communications address of the smart cooling product as planned. The NMS communicates with the smart cooling product using this address, and the communications addresses of two smart cooling products connected to the same NMS must be different.
RS485 monitoring grouping
- In non-grouping scenarios, set RS485 monitoring grouping to Enable for each unit.
- In grouping scenarios, set RS485 monitoring grouping to Enable for the unit with the COM/FE port connected, and Disable for other units.
Setting Communications Parameters (Modbus-TCP Protocol)
Context
This section applies to the scenario where the unit is connected to the NMS.
Procedure
- On the home screen, choose , and set the IP address, subnet mask, and gateway based on the actual plan.Figure 6-15 WAN IP Settings
The WAN IP address cannot be in the 192.168.245.X, 192.168.246.X, or 192.168.248.X network segment.
- On the home screen, choose .
Parameter
Description
Link mode
- Server: The smart cooling product works as the server and can connect to two clients for communication.
- Client: The smart cooling product works as the client and can connect to a remote server for communication.
- Server and client: The smart cooling product works as the server and can connect to two clients for communication. It also works as the client and can connect to a remote server for communication.
Client encryption
This parameter is configurable when Link mode involves Client.
NOTE:In the third-party NMS scenario, if the third-party NMS does not have a certificate or does not support encryption, you are advised to set this parameter to Disable for non-encrypted connection. For security purposes, encryption is enabled by default. You can configure encryption based on actual requirements and security scenario evaluation.
Server encryption
This parameter is configurable when Link mode involves Server.
NOTE:In the third-party NMS scenario, if the third-party NMS does not have a certificate or does not support encryption, you are advised to set this parameter to Disable for non-encrypted connection. For security purposes, encryption is enabled by default. You can configure encryption based on actual requirements and security scenario evaluation.
Encryption algorithm CBC
Specifies whether to use the CBC encryption algorithm. After the parameter setting is changed, the system automatically restarts. Exercise caution with the setting.
NMS IP address
Enter the actual IP address of the NMS. The IP addresses of the display board, client NMS, and server NMS must be unique.
This parameter is configurable when Link mode involves Client.
NMS port number
This parameter is configurable when Link mode involves Client.
- Connecting to the NetEco: Set this parameter to 32907 if Client encryption is enabled, or set it to 32906 if Client encryption is disabled.
- Connecting to other NMSs: You are advised not to change the value. In special cases, set this parameter based on the site requirements.
Pre-shared password
Secondary authentication password used for Modbus-TCP connection.
Setting Communications Parameters (SNMP Protocol)
Context
- To set communications parameters, log in as the admin user.
- This section is suitable only for SNMP. Skip this section if you use Modbus.
- Record the values entered in this section. They will be used when you connect a unit to a network management system (NMS).
- One unit supports concurrent access of up to 6 NMSs through SNMP.
Procedure
- On the home screen, choose .Figure 6-16 Setting SNMP communications parameters
- Set SNMP Version based on site requirements, and then tap Submit.
- When SNMP Version is set to ALL or SNMPv1&v2c, you can set Read Community and Write Community.
- When SNMP Version is set to ALL or SNMPv3, you can add an SNMPv3 user.
SNMPv1&SNMPv2c are insecure protocols. SNMPv3 is recommended.
- Set Read Community and Write Community.
- Tap the text box next to Read Community, set the read community parameter based on the actual plan, and tap Submit.
- Tap the text box next to Write Community, set the write community parameter based on the actual plan, and tap Submit.
- Add a SNMPv3 user.
- Tap the text box next to SNMP Port, set SNMP Port based on the actual port number, and tap Submit.
SNMP Port is set to 161 by default.
- Tap Next Page.
- Set SNMP trap parameters.
Follow-up Procedure
After a USB flash drive has been inserted into the USB port of the main control module and successfully identified, tap Export File under MIB File to export the MIB file to the USB flash drive for the customer's use in accessing a third-party NMS.
Before using a USB flash drive, ensure that its data has been scanned by antivirus software and is secure.
(Optional) Setting WiFi Parameters
Connect the mobile phone to the WiFi network and use the mobile phone app for power-on commissioning and software upgrade.
Prerequisites
After the WiFi module of the USB port is connected to the USB port on the main control module of the unit, WIFI Settings can be set.
Procedure
- On the home screen, choose .Figure 6-18 WIFI Setting
- Set parameters.
Parameter
Description
WiFi SSID
Set WiFi SSID based on the actual configuration; WiFi SSID is the name used for the WiFi hotspot over which a mobile phone can connect to the smart cooling product.
WiFi password
Enter the WiFi password when you use a mobile phone to connect to the WiFi. The WiFi has no preset password. When you enable the WiFi function for the first time, you need to set a password.
Enable WiFi
Enables the WiFi function of the smart cooling product. The default status is Disable.
WiFi group sharing enable
When a mobile phone is connected to the WiFi of the smart cooling product, it can access the units in the same FE cascading network.
- Tap Submit.