Checking the Outdoor Unit
Check Item |
Expected Result |
Actual Result |
---|---|---|
Rack |
The rack is installed properly, without any tilt. |
□ Passed □ Failed |
The rack is secured to the ground or base. |
||
Fans |
The fans are secured, and the blades rotate without block. |
□ Passed □ Failed |
Electrical control box |
The electrical control box is secured. |
□ Passed □ Failed |
The screws on the cover of the electrical control box are tightened. |
||
Cables are properly connected. |
||
Waterproof connectors are secured and properly sealed. |
||
Air tightness of the heat exchanger |
There is a sound of air flow when you press the needle valve. |
□ Passed □ Failed |
Fins of the heat exchanger |
The fins are not pushed down or damaged. |
□ Passed □ Failed |
Fins protection plates have been removed. |
||
Pipes |
Pipes are secured and not damaged. |
□ Passed □ Failed |
The needle valve cap has been tightened. |
||
Lay out the pipes properly, and cannot destroy the building structure and waterproof. |
||
Electric verification |
No cable is in contact with the copper pipe. |
□ Passed □ Failed |
Verify that the cables have been used protective casing and the cable outlet facing down. |
||
Verify that the terminal position is higher than the position of the connecting cable. |
||
Verify that the phase sequence of the outdoor unit output cables is correct. If the phase sequence is incorrect, the outdoor fan will rotate reversely. |
||
Waterproof connectors are tightened. Apply sealing putty when the waterproof connector on the outdoor unit side faces upward. |
||
Low temperature component (optional) |
Cables are securely tightened, and measures have been taken to prevent cables from sun exposure and water. |
□ Passed □ Failed |
The low temperature component is secured using bolts. |