Replacing a Display Module
Prerequisites
- A display module needs to be replaced.
- A spare display module of the same model (or BOM number) as the faulty display module is available.
Context
Recommended tools: Phillips screwdriver (M4) and ESD gloves
Preparation: Maintain from the front door.
Procedure
- (Optional) Back up data. If the WebUI or ECC is not configured, skip this step.
- Insert the USB flash drive into the main control board (or main control module). Go to as an admin user to back up data to the USB flash drive.
- Log in to the WebUI of the smart cooling product as an admin user. Choose . (Optional) After entering Configuration File Encryption Password, tap Back Up Current Settings to back up data to the computer.
- Log in to the WebUI of the ECC as an admin user. Choose Data Type to the smart cooling product. Tap Export Local Data of Southbound Devices to back up data to the computer. and set
- Replace the display module.
- Do not frequently or quickly disconnect and connect the DP cable of the display module. Do not forcibly pull the DP cable.
- You are advised to power off the main control board (or main control module) before replacing the display module.
- If the main control board is not powered off, you are advised to back up the configuration file of the product by referring to a or b.
- If the main control board is not powered off, the main control board detects and initializes the display module after the DP cable is connected to the display module. This process takes 10s to 30s. Wait for 5s to 10s. The indicator on the panel turns on, but the screen does not turn on. Wait for another 5s to 20s until the screen is restored to the state before the replacement.
- If the main control board is powered off, power on the main control board after the DP cable is connected to the display module. After the main control board is powered on, the startup logo and self-check progress bar are displayed on the display module. Then, the main screen is displayed. The whole restoration takes about 60s to 90s.
- (Optional) Import the configuration. If the WebUI or ECC is not configured, skip this step.
- Insert the USB flash drive into the main control board (or main control module). Go to as an admin user to import the backup data in the USB flash drive.
- Log in to the WebUI of the smart cooling product as an admin user. Choose Configuration File Encryption Password, tap Upload to import the data to the WebUI. , and choose the backup data. (Optional) After entering