Technical Specifications
Item |
Specifications |
---|---|
Refrigerant |
R410A |
Cooling capacitya |
46 kW |
Air supply mode |
Horizontal flow |
Airflow |
9000 m3/h |
Dimensions (H x W x D) |
|
IP rating |
IP20 |
a: Tested under rated working conditions (indoor dry-bulb temperature: 37°C, relative humidity: 20%, outdoor temperature: 35°C). |
Item |
NetCol5000-A050H4WD2 |
NetCol5000-A050H40D2 |
NetCol5000-A050H4WE2 |
NetCol5000-A050H40E2 |
NetCol5000-A050HRWE2 |
NetCol5000-A050H4WE0 |
NetCol5000-A050H40E0 |
---|---|---|---|---|---|---|---|
Power system |
380–415 V AC, 50/60 Hz, 3 Ph+N+PE Tolerance: –10% to +10% of rated voltage, rated frequency±3 Hz |
440–480 V AC, 60 Hz, 3 Ph+PE Tolerance: –10% to +10% of rated voltage, rated frequency±3 Hz |
380–415 V AC, 50/60 Hz, 3 Ph+N+PE Tolerance: –10% to +10% of rated voltage, rated frequency±3 Hz |
||||
Power supply mode |
Dual power supplies |
Single power supply |
|||||
Pipe routing |
Top and bottom pipe routing |
Bottom pipe routing |
|||||
Maximum current |
46 A |
36 A |
46 A |
||||
Condensate pump |
Yes |
No |
|||||
Water pump lift |
4 m |
- |
|||||
Heating function |
Yes |
No |
Yes |
No |
Yes |
Yes |
No |
Humidification function |
Yes |
No |
Yes |
No |
Yes |
Yes |
No |
Humidifier water inlet hose |
No |
No |
Yes |
No |
Yes |
Yes |
No |
Reheating capacity |
6 kW |
No |
6 kW |
No |
6 kW |
6 kW |
No |
Connection mode of the compressor and filter dryer |
Welding |
Thread connection |
|||||
Castor |
No |
Yes |
|||||
Humidification capacity |
3 kg/h |
No |
3 kg/h |
No |
3 kg/h |
3 kg/h |
No |
Net weight/Gross weight |
314.5 kg/331.5 kg |
312 kg/329 kg |
318 kg/346 kg |
323 kg/340 kg |
305 kg/333 kg |
309 kg/337 kg |
314.5 kg/331.5 kg |
Item |
NetCol500-A060 |
NetCol500-A080 |
NetCol500-A120 |
---|---|---|---|
BOM number |
NetCol500-A060MC1D0: 52273539, 52273539-005, 52273539-007, 52273539-008 NetCol500-A060MS1E0: 52273539-006 |
NetCol500-A080MC1D0: 52273541-005, 52273541-009 |
NetCol500-A120MC1D0: 52273755-002, 52273755-003 |
Power supply mode |
Powered by the indoor unit |
||
Temperature control intelligent monitoring board |
52273539 and 52273539-007: available 52273539-005, 52273539-008, and 52273539-006: unavailable |
52273541-005 and 52273541-009: unavailable |
52273755-002 and 52273755-003: unavailable |
Operating temperature range |
–20°C to +45°C (–40°C to +45°C with a low temperature component) |
–5°C to +55°C |
–20°C to +45°C (–40°C to +45°C with a low temperature component) |
Fan speed range |
10%–100% |
||
Number of fans |
1 |
2 |
2 |
Dimensions (H1 (H2) x W1 (W2) x D) (mm) |
BOM numbers 52273539 and 52273539-007: 1107 (677) x 1356 (1217) x 1094 BOM numbers 52273539-005 and 52273539-008: 1107 (655) x 1356 (1217) x 1094 BOM number 52273539-006: 1156 (703) x 1356 (1217) x 1094 |
BOM numbers 52273541-005 and 52273541-009: 1107 (655) x 2186 (2047) x 1094 |
BOM numbers 52273755-002 and 52273755-003: 1107 (655) x 1356 (1217) x 2188 |
Net weight |
52273539 and 52273539-007: 122 kg 52273539-005 and 52273539-008: 121 kg 52273539-006: 154 kg |
52273541-005 and 52273541-009: 200 kg |
52273755-002 and 52273755-003: 265 kg |
Storage temperature |
–40°C to +70°C |
||
Storage humidity |
5%–95% RH (non-condensing) |
||
IP rating |
IPX5 |
||
Altitude |
0–4000 m. If the altitude exceeds 1000 m, the cooling performance is derated. For details about derating data, contact technical support. |
Type |
Description |
---|---|
Class A (controlled environment) |
Indoor environments where the temperature and humidity are controlled, including rooms where human beings live |
Class B (uncontrolled environment) |
Indoor environment where the ambient temperature and humidity are not controlled or outdoor environments (with simple shielding measures) where the humidity can reach 100%. |
Class C (harsh environment) |
Sea environments or outdoor land environments (with simple shielding measures) near pollution sources. Pollution sources refer to the following areas:
|
Class D (marine environment) |
Areas within 500 m away from the seashore. |
- If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B environment, it is recommended that the unit be installed in a shielded area, such as a podium building, ground, or building rear, to prevent mechanical parts from being corroded by sea wind (the functionality and reliability of the system must not be affected). Alternatively, use an outdoor unit that supports class C environments to avoid corrosion. If the site is more than 10 km away from the coast, the unit can be properly installed.
- The NetCol500-A060MS1E0 outdoor unit must not be installed in class D environments, and other outdoor units must not be installed in class C or class D environments.
Item |
Technical Specifications |
---|---|
Power system |
220–240 V AC, 1 Ph+N+PE, 50/60 Hz |
Refrigerant |
R410A |
Heat exchanging capacity |
55 kW |
Temperature range |
4°C to 45°C |
Humidity range |
5%–90% RH |
Storage temperature |
–40°C to +70°C |
Storage humidity |
5%–95% RH (non-condensing) |
Inlet water temperature range of chilled water |
10°C to 37°C |
Maximum operating temperature on the refrigerant side |
125°C |
Maximum operating temperature on the cooling water side |
60°C |
Water flow rate |
9.5 m3/h |
Water-side pressure bearing |
1.2 MPa |
Refrigerant-side pressure bearing |
4.35 MPa |
IP rating |
IP21 |
Altitude |
0–4000 m (derated when the altitude is greater than 1000 m) |
Environment |
Enclosed indoor environment in which the temperature and humidity can be controlled within the ranges of 4°C to 45°C and 5% RH to 90% RH respectively. If the indoor installation position is ventilated, it should be more than 3.7 km away from the sea or pollution sources (such as salt lakes, chemical plants, mineral plants, thermal power plants, and coal mines). |
Net weight |
63 kg |