Wizard Startup
Wizard Startup
Check that refrigerant is fully charged before performing the wizard startup.
Wizard Startup allows you to commission the indoor and outdoor fans, electric heater, humidifier, condensate pump, and cooling system, and supports automatic running and judgment of components.
After you power on the smart cooling product for the first time, the Wizard Startup screen is displayed. If the smart cooling product is not started for the first time, choose Maint > Wizard Startup to enter the Wizard Startup screen.
Tapping No or Exit, a submission timeout, and a system exception all result in commissioning failures. Choose Maint > Wizard Startup to enter the Wizard Startup screen and start the commissioning again.
On the home screen, choose Maint > Wizard Startup and tap Yes to enter the screen for checking before startup.
Figure 6-23 Wizard Startup
For the initial wizard startup, Last Record is in gray, indicating that operation is not allowed.
For a non-initial wizard startup, you can choose Last Record to view the last wizard startup report.
Figure 6-24 Checking before startup
Follow the onscreen instructions to complete the wizard startup.
If electric heaters and humidifiers are not configured, the electric heater commissioning and humidifier commissioning items are not displayed.
If the heating and humidification functions are disabled, the electric heater commissioning and humidifier commissioning items cannot be selected.
All the items are selected by default if you enter the screen for selecting commissioning items for the first time. You can clear commissioning items that are not required.
After the fan commissioning, the electric heater commissioning screen is displayed. Use a clamp meter to measure the current of the cable connected to the KM4 terminal, enter the value on the screen, and tap Submit within the time displayed on the screen. The system automatically determines whether the current of the smart cooling product is within the normal range.