(Optional) Installing the Humidifier Water Inlet Pipe
Installing the Humidifier Water Inlet Pipe (With a Humidifier Hose)
Bottom Pipe Routing
- Straighten the water inlet pipe delivered with the smart cooling product, and route it from the inside to the outside through the water inlet hole at the bottom of the smart cooling product.Figure 4-72 Bottom routing of the water inlet pipe
The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a hose or rigid pipe based on site requirements.
- Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to avoid impurities entering into the humidifier.
- Connect the water inlet pipe to the engineering pipe and wrap the pipe with thermal insulation foam.
Top Pipe Routing
When routing pipes from the top, do not route the pipes over servers or other devices to protect them from being affected by pipe leaks.
- Straighten the water inlet pipe delivered with the smart cooling product, and route it from the inside to the outside through the water inlet hole on the top of the smart cooling product.Figure 4-73 Top routing of the water inlet pipe
- The other end is a reserved G 1/2 inch connector with inner screw threads. Connect the other end to a hose or rigid pipe based on site requirements.
- Secure the water inlet pipe inside the cabinet to the left post of the cabinet using cable ties.
- Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to avoid impurities entering into the humidifier.
- Connect the water inlet pipe to the engineering pipe and wrap the pipe with thermal insulation foam.
Installing the Humidifier Water Inlet Pipe (Without a Humidifier Hose)
Procedure
- Melt the active connector with rigid pipe 1 and the elbow to form a water supply pipe assembly, as shown by (1) and (2) in the following figure.
- Connect the water supply pipe assembly to the water inlet solenoid valve, as shown by (3) in the following figure.
- Melt rigid pipe 2 and the water supply pipe assembly, as shown by (4) in the following figure.
The other end is a reserved φ25 mm connector. Connect the other end to a hose or rigid pipe based on site requirements.
Figure 4-74 Connecting a humidifier water inlet pipe - Clean the engineering pipes before connecting the water inlet pipe to the engineer pipe to avoid impurities entering into the humidifier.
- Connect the water inlet pipe to the engineering pipe and wrap the pipe with thermal insulation foam.Figure 4-75 Top routing of the water inlet pipeFigure 4-76 Bottom routing of the water inlet pipe
When routing pipes from the top, do not route the pipes over servers or other devices to protect them from being affected by pipe leaks.