Refrigerant Charge Amount
Refrigerant Charge Amount |
Actual One-Way Pipe Length (L) |
NetCol500-A060 (NetCol500-A120) |
NetCol500-A060 with a Low Temperature Component |
NetCol500-A080 |
NetCol500-W055 |
---|---|---|---|---|---|
Standard charge amount (kg) |
≤ 10 m |
9.2 |
35.8 |
13.2 |
10 |
Charge amount (kg) = Standard charge amount + Extra charge amount |
10 m < L ≤ 60 m |
9.2 + (L – 10) x 0.19 |
35.8 + (L – 10) x 0.19 |
13.2 + (L – 10) × 0.19 |
10 + (L – 10) × 0.21 |
Charge amount (kg) = Standard charge amount + Extra charge amount |
60 m < L ≤ 100 m |
9.2 + (L – 10) x 0.25 |
35.8 + (L – 10) x 0.25 |
13.2 + (L – 10) × 0.25 |
10 + (L – 10) × 0.28 |
When the outdoor unit is NetCol500-A120, two indoor units can be connected.