SmartLogger3000 User Manual

This document describes the SmartLogger3000 and SmartModule1000A01 in terms of installation, electrical connections, system operation, maintenance, and troubleshooting. BOM number: 02312SCU, 02312SCU-001, 02312SCU-002, 02312SCU-003, 02312SCU-004, 02312SCU-005, 02312SCU-006, 02312SCU-007, 02312SCU-008, 02312SCU-009, 02312SCU-010, 02312SGF, 02312SGG, 02312SGK and 02312SGJ.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Setting Remote Shutdown

Setting Remote Shutdown

Context

The SmartLogger provides four DI ports. The OVGR can connect to any DI port. The SmartLogger shuts down the solar inverter over OVGR signals.

Figure 6-51 Networking

When setting this function, ensure that the user-defined DI port is not occupied. Otherwise, the setting will fail.

Procedure

  1. Set remote shutdown parameters.

    Figure 6-52 Remote shutdown

    Parameter

    Description

    connection port

    Set this parameter to the DI port connected to OVGR signals.

    Effective dry contact status

    The value can be Open or Close.

    NOTE:

    If OVGR shutdown is enabled and this parameter is set to Close, the SmartLogger sends a solar inverter shutdown command only when the corresponding DI port is in the Close state.

    OVGR shutdown

    Specifies whether to enable shutdown over OVGR.

    Cubicle alarm enabling

    If this parameter is set to Enable, the Abnormal Cubicle alarm is raised when the dry contact signal is effective and the Cubicle is abnormal.