This document describes the SmartLogger3000 and SmartModule1000A01 in terms of installation, electrical connections, system operation, maintenance, and troubleshooting. BOM number: 02312SCU, 02312SCU-001, 02312SCU-002, 02312SCU-003, 02312SCU-004, 02312SCU-005, 02312SCU-006, 02312SCU-007, 02312SCU-008, 02312SCU-009, 02312SCU-010, 02312SGF, 02312SGG, 02312SGK and 02312SGJ.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Technical Specifications of the SmartModule

Technical Specifications of the SmartModule

Device Management

Parameter

Specifications

Communications mode

RS485, ETH

Maximum communication distance

  • RS485:1000 m
  • ETH: 100 m

Common Specifications

Parameter

Specifications

DC power supply

  • DC 12 V: DC 2.0 power socket male connector
  • DC 24 V: cord end terminal

Power consumption

Typical: 4 W; maximum: 5 W

Dimensions (H x W x D)

  • Including mounting ears: 160 mm x 179 mm x 59 mm
  • Without mounting ears: 160 mm x 125 mm x 44 mm

Net weight

1 kg

Operating temperature

–40°C to +60°C

Storage temperature

–40°C to +70°C

Humidity

5%–95% RH

Ingress protection rating

IP20

Installation mode

Installed on a wall or guide rail

Maximum operating altitude

4000 m

Pollution level

Level 2

Corrosion level

Class B

Ports

Parameter

Specifications

Ethernet electrical port (GE)

4 PCS; 10M/100M/1000M auto-negotiation

RS485 port (COM)

3 PCS; supported baud rates: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19,200 bit/s, and 115,200 bit/s

Power output port

1 PCS; DC output: 12 V, 0.1 A

Digital input (DI) port

4 PCS; supports only the access from relay dry contacts

PT port (PT)

Two PCS; supports the access of signals from a 3-wire or 2-wire PT100/PT1000 temperature sensor

Analog input (AI) port

4 PCS; AI1: supports 0–10 V voltage (passive); AI2–AI4: support 4–20 mA or 0–20 mA input current (passive)