Setting IEC 104 Device Parameters
Context
The SmartLogger can connect to third-party devices that support the IEC 104 protocol, such as relay protection or measurement and control devices such as transformer stations. The protocol information points vary depending on vendors. Therefore, you need to configure a protocol information file in .cfg format. To connect devices to the SmartLogger, the supplier or Huawei engineers need to modify the parameters in the device configuration table file delivered with the version based on device requirements, generate a protocol information file in .cfg format, and import the file to the SmartLogger.
The supported device types are IEC104 Device 1 to IEC104 Device 5. The corresponding configuration file names are iec104_equip_custom_1.cfg to iec104_equip_custom_5.cfg. Multiple devices of the same type can be connected.
Procedure
- Configure the protocol information point file in .cfg format and import the file to the SmartLogger.Figure 6-61 Importing configuration
- Click Add Devices and set access parameters.Figure 6-62 Setting access parameters
Parameter
Description
Device Type Currently, IEC104 Device 1 to IEC104 Device 5 are supported.
Set this parameter based on the configuration import file. For example, if you import iec104_equip_custom_1.cfg, select IEC104 Device 1.
IP address Set this parameter to the IP address of the IEC 104 device.
Common address Set this parameter to the common address of the IEC 104 device.
Address Set this parameter to the communications address of the IEC 104 device.
- Set monitoring parameters and click Submit.Figure 6-63 Monitoring
Tab
Function
Setting
Running Info. Displays the running information about the IEC 104 device.
-
Teleindication Displays the device status, such as the switch status.
-
Telemetering Displays the real-time analog data of the device, such as the voltage.
-
Telecontrol Allows users to set status control parameters, such as the parameter for controlling switch-on or switch-off.
Set this parameter as required.
Teleadjust Allows users to set analog parameters, such as voltage protection parameters.
Set this parameter as required.