This document describes the SmartLogger3000 and SmartModule1000A01 in terms of installation, electrical connections, system operation, maintenance, and troubleshooting. BOM number: 02312SCU, 02312SCU-001, 02312SCU-002, 02312SCU-003, 02312SCU-004, 02312SCU-005, 02312SCU-006, 02312SCU-007, 02312SCU-008, 02312SCU-009, 02312SCU-010, 02312SGF, 02312SGG, 02312SGK and 02312SGJ.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Setting IEC104 Device Parameters

Setting IEC104 Device Parameters

Context

The SmartLogger can connect to third-party devices that support IEC104, such as the relay protection or monitoring device like the transformer substation. Protocol information points vary with vendors. Therefore, you need to configure a protocol information point file in .cfg format and import the file to the SmartLogger for connecting to a third-party device.

The supported device types are IEC104 device 1 to IEC104 device 5. The corresponding configuration file names are iec104_equip_custom_1.cfg to iec104_equip_custom_5.cfg. Multiple devices of the same type can be connected.

Procedure

  1. Configure a protocol information point file in .cfg format and import the file to the SmartLogger.

    Figure 6-40 Importing configuration

  2. Set access parameters and click Add Devices.

    Figure 6-41 Setting access parameters

    Parameter

    Description

    Device Type

    The value can be IEC104 Device 1 to IEC104 Device 5.

    Select a value based on the imported configuration file. For example, if iec104_equip_custom_1.cfg is imported, select IEC104 Device 1.

    IP address

    Set this parameter to the IP address of the IEC104 device.

    Common address

    Set this parameter to the common address of the IEC104 device.

    Address

    Set this parameter to the communications address of the IEC104 device.

  3. Set device monitoring parameters and click Submit.

    Figure 6-42 Device monitoring

    Tab

    Function

    Description

    Running Info.

    View the running information about the custom device.

    N/A

    Teleindication

    View the device status, such as the switch status.

    N/A

    Telemetering

    View the real-time analog data of the device, such as the voltage.

    N/A

    Telecontrol

    Set the status control parameters, such as the parameters for turning on or off switches.

    Set the parameters on the tab page as required.

    Teleadjust

    Set analog parameters, for example, set voltage protection parameters.

    Set the parameters on the tab page as required.