Setting IEC104 Device Parameters
Context
The SmartLogger can connect to third-party devices that support IEC104, such as the relay protection or monitoring device like the transformer substation. Protocol information points vary with vendors. Therefore, you need to configure a protocol information point file in .cfg format and import the file to the SmartLogger for connecting to a third-party device.
The supported device types are IEC104 device 1 to IEC104 device 5. The corresponding configuration file names are iec104_equip_custom_1.cfg to iec104_equip_custom_5.cfg. Multiple devices of the same type can be connected.
Procedure
- Configure a protocol information point file in .cfg format and import the file to the SmartLogger.Figure 6-76 Importing configuration
- Set access parameters and click Add Devices.Figure 6-77 Setting access parameters
Parameter
Description
Device Type The value can be IEC104 Device 1 to IEC104 Device 5.
Select a value based on the imported configuration file. For example, if iec104_equip_custom_1.cfg is imported, select IEC104 Device 1.
IP address Set this parameter to the IP address of the IEC104 device.
Common address Set this parameter to the common address of the IEC104 device.
Address Set this parameter to the communications address of the IEC104 device.
- Set device monitoring parameters and click Submit.Figure 6-78 Device monitoring
Tab
Function
Description
Running Info. View the running information about the custom device.
N/A
Teleindication View the device status, such as the switch status.
N/A
Telemetering View the real-time analog data of the device, such as the voltage.
N/A
Telecontrol Set the status control parameters, such as the parameters for turning on or off switches.
Set the parameters on the tab page as required.
Teleadjust Set analog parameters, for example, set voltage protection parameters.
Set the parameters on the tab page as required.