Setting MBUS Parameters
Setting Parameters for a Built-in MBUS Module
Procedure
- Set access parameters.Figure 6-41 Setting parameters for a built-in MBUS module
Parameter
Description
Built-in MBUS
- When the SmartLogger communicates with the inverter using a built-in MBUS module, set this parameter to Enable.
- When the SmartLogger communicates with the inverter and third-party device only over RS485, set this parameter to Disable.
Device disconnection time
Specifies the device disconnection time.
- Set networking parameters.
Tab |
Parameter |
Description |
---|---|---|
Running Param. |
Anti-crosstalk |
Set this parameter to Enable. When the transformer station number and winding number of the inverter are the same as those of the MBUS, or the inverter SN is in the SN list, the inverter can connect to the SmartLogger over an MBUS network. |
Network frequency band |
Set this parameter based on site requirements. |
|
Box-type transformer No. |
Set this parameter based on the number of the transformer station connected to the SmartLogger. |
|
Winding No. |
In the scenario of multi-split transformer stations, set this parameter based on the winding number of the transformer station connected to the SmartLogger. |
|
Networking |
|
|
Power settings |
This parameter is used to adjust the transmit power of MBUS signals. A larger value indicates higher transmit power and better networking capabilities. The default value is 8 (NA is displayed). You can set this parameter based on actual requirements. |
|
Transmit mode[1] |
|
|
Fast control frame type[2] |
|
|
Fast scheduling[3] |
Set this parameter based on the actual networking.
|
|
- |
|
|
Note [1]: This parameter can be set only in SmartMBUS V100R001C00SPC212 and later versions. Note [2]: This parameter can be set only in SmartMBUS V100R001C00SPC212 and later versions, but has been deleted in SmartMBUS V100R001C00SPC220 and later versions. Note [3]: This parameter can be set only in SmartMBUS V100R001C00SPC220 and later versions. |
Setting Parameters for an External MBUS Module
Set parameters for an external MBUS module based on the model of the connected device. The models of external MBUS modules include SmartMBUS CCO01A and SmartMBUS CCO01B.
Setting SmartMBUS CCO01A Parameters
Procedure
- Set access parameters.
- Method 1: Click Auto. Search to connect to the MBUS module.
- Method 2: Click Add Devices, set access parameters, and click Add Devices.
Figure 6-43 Setting access parameters for an external MBUS moduleParameter
Description
Device Type
Set this parameter to MBUS.
Port number
Set this parameter to the COM port connected to the MBUS module.
- Set networking parameters.
Tab |
Parameter |
Description |
---|---|---|
Running Param. |
Baud rate |
Retain the default value 115200 to achieve better communication performance. |
Anti-crosstalk |
Set this parameter to Enable. When the transformer station number and winding number of the inverter are the same as those of the MBUS, or the inverter SN is in the SN list, the inverter can connect to the SmartLogger over an MBUS network. |
|
Network frequency band |
Set this parameter based on site requirements. |
|
Box-type transformer No. |
Set this parameter based on the number of the transformer station connected to the SmartLogger. |
|
Winding No. |
In the scenario of multi-split transformer stations, set this parameter based on the winding number of the transformer station connected to the SmartLogger. |
|
Networking |
|
|
Power settings |
This parameter is used to adjust the transmit power of MBUS signals. A larger value indicates higher transmit power and better networking capabilities. The default value is 8 (NA is displayed). You can set this parameter based on actual requirements. |
|
Transmit mode[1] |
|
|
Network interface[1] |
|
|
IP address[1] |
IP address of the MBUS module. The default value is 192.168.8.249. Change the value only when an IP address conflict occurs. |
|
Fast control frame type[2] |
|
|
Fast scheduling[3] |
Set this parameter based on the actual networking.
|
|
SN List |
- |
|
Note [1]: This parameter can be set only in SmartMBUS V100R001C00SPC212 and later versions. Note [2]: This parameter can be set only in SmartMBUS V100R001C00SPC212 and later versions, but has been deleted in SmartMBUS V100R001C00SPC220 and later versions. Note [3]: This parameter can be set only in SmartMBUS V100R001C00SPC220 and later versions. |
Setting SmartMBUS CCO01B Parameters
The SmartLogger3000 software versions of V300R023C00SPC110 and later support FE access.
Procedure
- (Optional) If the SmartMBUS CCO01B is installed in the STS, set Built-in MBUS to Disable on the SmartLogger3000, as shown in Figure 6-45. If the SACU model is SmartACU2000D-D-02 or SmartACU2000D-D-03, remove the power supply to disable the CCO module installed in the SACU to prevent communications interference between the two CCO modules. If the preceding conditions are not met, skip this step.
- Set access parameters.
- If FE communication is selected for the SmartMBUS CCO01B, the SmartMBUS CCO01B is automatically added.
- If RS485 communication is selected for the SmartMBUS CCO01B, you have two methods to add a device.
Method 1: Click Auto. Search to connect to the MBUS module.
Method 2: Click Add Devices, set access parameters, and click Add Devices.
Figure 6-46 Setting access parameters for an external MBUS moduleParameter
Description
Device Type
Set this parameter to MBUS.
Port number
Set this parameter to the COM port connected to the MBUS module.
- Set networking parameters.
Tab |
Parameter |
Description |
---|---|---|
Running Param. |
Baud rate |
Retain the default value 115200 to achieve better communication performance. This parameter is set only when the SmartMBUS CCO communication mode is set to RS485. |
Anti-crosstalk |
Set this parameter to Enable. When the transformer station number and winding number of the inverter are the same as those of the MBUS, or the inverter SN is in the SN list, the inverter can connect to the SmartLogger over an MBUS network. |
|
Box-type transformer No. |
Set this parameter based on the number of the transformer station connected to the SmartLogger. |
|
Winding No. |
In the scenario of multi-split transformer stations, set this parameter based on the winding number of the transformer station connected to the SmartLogger. |
|
Networking |
|
|
Power settings |
This parameter is used to adjust the transmit power of MBUS signals. A larger value indicates higher transmit power and better networking capabilities. The default value is 8 (NA is displayed). You can set this parameter based on actual requirements. |
|
Fast scheduling |
Set this parameter based on the actual networking.
|
|
Network frequency band |
Retain the default value. If you have any questions, contact the supplier or technical support. |
|
SN List |
- |
|