Setting CMU Parameters
This section does not apply to V300R001C00.
Procedure
ChooseSubmit.
, set running parameters and clickTemperature and Humidity Control
Parameter |
Setting Description |
---|---|
|
|
At the first startup after deployment or long-term storage, you are advised to start forced dehumidification to reduce the risk of equipment damage caused by condensation. |
Exhaust Control
Parameter |
Setting Description |
---|---|
Exhaust fan control module self-test time |
Time when the exhaust function is self-checked every day |
Exhaust fan control module self-test |
After the exhaust function self-check is started, the exhaust fan will turn on for a period of time and the exhaust fan will be check. If the exhaust fan does not meet the exhaust function requirements, the system cannot start. |
After started, the exhaust fan will automatically stop in 1 hour. If a combustible gas alarm is generated, the exhaust fan cannot be stopped. The exhaust fan cannot be manually started after the fire response is triggered until the fire alarm is cleared or 24 hours later. |
Fire Suppression
Only the LUNA2000-2.0MWH Series Smart String ESS supports DC output power distribution.
Parameter |
Setting Description |
---|---|
|
Only the LUNA2000-200KWH Series Smart String ESS supports the temperature alarm threshold settings.
Parameter |
Setting Description |
---|---|
Specifies the temperature threshold for triggering a fire alarm and processing fire response logic. |