Setting Custom Device Parameters
Context
The SmartLogger can connect to third-party devices supporting the Modbus RTU protocol, such as transformer stations and EMIs. The protocol information points vary depending on vendors. Therefore, you need to configure a protocol information file in .cfg format. To connect devices to the SmartLogger, the supplier or Huawei engineers need to modify the parameters in the device configuration table file delivered with the version based on device requirements, generate a protocol information file in .cfg format, and import the file to the SmartLogger.
The supported device types are Custom Device1 to Custom Device10. The corresponding configuration file names are modbus_equip_custom_1.cfg to modbus_equip_custom_10.cfg. Multiple devices of the same type can be connected.
Procedure
- Configure the protocol information point file in .cfg format and import the file to the SmartLogger.Figure 6-64 Importing configuration
- Click Add Devices and set access parameters.Figure 6-65 Setting access parameters
Parameter
Setting
Device Type Currently, Custom Device1 to Custom Device10 are supported.
Set this parameter based on the configuration import file. For example, if you import modbus_equip_custom_1.cfg, select Custom Device1.
Port number Set this parameter to the number of the COM port connected to the custom device.
Address Set this parameter to the communications address of the custom device.
- Set monitoring parameters and click Submit.Figure 6-66 Monitoring
Tab
Function
Setting
Running Info. Displays the running information about the custom device.
-
Teleindication Displays the device status, such as the switch status.
-
Telemetering Displays the real-time analog data of the device, such as the voltage.
-
Telecontrol Allows users to set status control parameters, such as the parameter for controlling switch-on or switch-off.
Set this parameter as required.
Teleadjust Allows users to set analog parameters, such as voltage protection parameters.
Set this parameter as required.