Setting Capacity Limit
Context
- Capacity limit scenarios in TOU mode:
When Capacity Limit is enabled in TOU mode, the charge/discharge duration set in the TOU window must be 24 hours. Capacity Limit is not supported in non-charge/discharge time.
- Other capacity limit scenarios:
- If the capacity limit is met 24 hours a day, the ratio of the ESS/Smart PCS to the load power must be properly set to ensure that the ESS/Smart PCS have sufficient capacity to meet the capacity limit.
- When the ESS is used only for capacity limit, you can set the charge window to 24 hours by setting TOU. Do not set the discharge window and non-charge/discharge window.
- The overload capacity of transformers, power distribution switches, and lines must be greater than the sum of the maximum charge current and maximum load current of the ESSs.
Procedure
Parameter |
Setting Description |
---|---|
If this parameter is set, the capacity of the grid-connection point is not limited. The inverter and PCS run according to the preset control policy. |
|
If this parameter is set, the active power of the grid-connection point for purchasing or feeding power cannot exceed the preset capacity limit. |
|
If this parameter is set, the apparent power of the grid-connection point for purchasing or feeding power cannot exceed the preset capacity limit. |
Active Capacity Limit
Parameter |
Setting Description |
---|---|
Set this parameter according to the charging capacity in the demand contract of the power grid company. Once set, the active power of the grid-connection point for purchasing or feeding power cannot exceed the preset value. |
|
Specifies the active power limit of the inverter when the feed-in meter communication is abnormal. You can manually change the active power percentage of the inverter as required. |
|
Specifies the active power limit of the PCS when the feed-in meter communication is abnormal. You can manually change the active power percentage of the PCS as required. |
Apparent Capacity Limit
Parameter |
Setting Description |
---|---|
Set this parameter according to the charging capacity in the demand contract of the power grid company. Once set, the apparent power of the grid-connection point for purchasing or feeding power cannot exceed the preset value. |
|
Specifies the active power limit of the inverter when the feed-in meter communication is abnormal. You can manually change the active power percentage of the inverter as required. |
|
Specifies the active power limit of the PCS when the feed-in meter communication is abnormal. You can manually change the active power percentage of the PCS as required. |