Setting Reactive Power Control
Large-scale plants are required to adjust the voltage at the grid-connection point. Power grid scheduling personnel enable a plant to absorb or add reactive power at the grid-connection point, that is, to enable the reactive power compensation, based on the real-time reactive power transmission status in the power grid.
- Choose Remote power schedule is set to Enable. . On the page that is displayed, check that
- Set the parameters for reactive power control and click Submit.Figure 6-72 Reactive power control
No Output
Parameter |
Description |
---|---|
If the plant is not required to adjust the voltage at the grid-connection point or perform reactive power compensation, device can run with pure active power output. In this case, set this parameter to No output. |
DI Reactive Scheduling
- When setting this function, ensure that the user-defined DI port is not occupied. Otherwise, the setting will fail.
- SmartLogger scenario: Before setting this function, ensure that the SmartLogger is properly connected to the ripple control receiver.
- SmartLogger+SmartModule scenario: Before setting this function, ensure that the SmartModule is properly connected to the ripple control receiver.
Parameter |
Description |
---|---|
Set this parameter to DI reactive scheduling. |
|
NOTE:
DI parameters include DI1, DI2, DI3, DI4, and Power factor. |
|
Parameter |
Description |
---|---|
Set this parameter to DI reactive scheduling. |
|
NOTE:
The DI parameters include M1.DI1, M1.DI2, M1.DI3, M1.DI4, and Percentage. |
|
- Before connecting the SmartModule to the SmartLogger, if DI reactive scheduling has been configured for the DI port and the scheduling signal needs to be connected to the SmartModule, delete the DI configuration and reconfigure it.
- In the scenario where the SmartLogger and SmartModule are combined, if the SmartModule is removed and the scheduling signal needs to be connected to the SmartLogger, delete the DI configuration and reconfigure it.
Reactive Power Fix Control
Parameter |
Description |
---|---|
If the PV array is required to generate constant reactive power at a specified time, set this parameter to Reactive power fix control. |
|
If the device is required to run with specified maximum power in certain periods of a day, add records based on site requirements. When multiple time points are set, the device will run with the maximum power specified for the time point that is earlier than and the closest to the current system time. For example, if you add 00:00:00 and 12:00:00 on the WebUI and the current system time is 14:30:00, the device will run with the maximum power specified for 12:00:00. |
|
Power Factor Fix Control
Parameter |
Description |
---|---|
If the plant is required to generate a constant power factor at the grid-connection point and the device is required to adjust the real-time reactive power based on the preset power factor, set this parameter to Power factor fix control. |
|
If the device is required to run with specified power in certain periods of a day, add records based on site requirements. When multiple time points are set, the device will run with the power specified for the time point that is earlier than and the closest to the current system time. For example, if you add 00:00:00 and 12:00:00 on the WebUI and the current system time is 14:30:00, the device will run with the maximum power specified for 12:00:00. |
|
Q-U Characteristic Curve
If the remote reactive power control command is not available, you can configure the characteristic curve as a substitute. The SmartLogger delivers the values configured for the characteristic curve to the inverter or Smart PCS, which then operates according to the configuration. The SmartLogger no longer adjusts the values.
Configure the characteristic curve under instructions from professionals to ensure that the inverter or Smart PCS works properly.
In the Q-U characteristic curve control mode, the inverter or Smart PCS dynamically adjusts the ratio Q/S of output reactive power to apparent power in accordance with the ratio U/Un(%) of the actual grid voltage to the rated grid voltage.
Parameter |
Description |
---|---|
Set this parameter to Q-U characteristic curve. |
|
Specifies the change interval of the reactive power for a grid-tied point. |
|
Under a specific grid code, the characteristic curve takes effect only when the actual output active power of the device is greater than the specified value. |
|
Under a specific grid code, the characteristic curve becomes invalid when the actual output active power of the device is less than the specified value. |
|
Limits the actual minimum PF when the Q-U characteristic curve takes effect. |
|
Specifies the number of characteristic curve points. The characteristic curve supports a maximum of 10 valid points. |
|
When configuring the curve, ensure that the U/Un(%) value of a point is greater than the U/Un(%) value of the previous point. Otherwise, the message indicating invalid input will be displayed. |
|
cosφ-P/Pn Characteristic Curve
If the remote reactive power control command is not available, you can configure the characteristic curve as a substitute. The SmartLogger delivers the values configured for the characteristic curve to the inverter or Smart PCS, which then operates according to the configuration. The SmartLogger no longer adjusts the values.
Configure the characteristic curve under instructions from professionals to ensure that the inverter or Smart PCS works properly.
In the cosφ-P/Pn characteristic curve control mode, the inverter or Smart PCS dynamically adjusts the power factor cosφ in accordance with the P/Pn (%) based on the VDE-4105 and BDEW German standards.
Parameter |
Description |
---|---|
Set this parameter to cosφ-P/Pn characteristic curve. |
|
Specifies the change interval of the reactive power at the grid-connection point. |
|
Specifies the number of characteristic curve points. The characteristic curve supports a maximum of 10 valid points. |
|
When configuring the curve, ensure that the P/Pn(%) value of a point is greater than the P/Pn(%) value of the previous point. Otherwise, the message indicating invalid input will be displayed. |
|
Q-U Hysteresis Curve (CEI0-16)
If the remote reactive power control command is not available, you can configure the characteristic curve as a substitute. The SmartLogger delivers the values configured for the characteristic curve to the inverter or Smart PCS, which then operates according to the configuration. The SmartLogger no longer adjusts the values.
Configure the characteristic curve under instructions from professionals to ensure that the inverter or Smart PCS works properly.
The Q-U hysteresis curve (CEI0-16) control mode is the Italian standard CEI0-16 version of the Q-U characteristic curve. It dynamically adjusts the output reactive power of the inverter or Smart PCS in accordance with the ratio of the actual voltage to the rated voltage. The target value of reactive power adjustment should be in the form of Q/S.
Parameter |
Description |
---|---|
Set this parameter to Q-U hysteresis curve(CEI0-16). |
|
Specifies the change interval of the reactive power for a grid-tied point. |
|
Under a specific grid code, the characteristic curve takes effect only when the actual output active power of the device is greater than the specified value. |
|
Under a specific grid code, the characteristic curve becomes invalid when the actual output active power of the device is less than the specified value. |
|
Limits the actual minimum PF when the Q-U characteristic curve takes effect. |
|
When configuring the curve, ensure that the U/Un(%) value of a point is greater than the U/Un(%) value of the previous point. Otherwise, the message indicating invalid input will be displayed. When configuring the curve, ensure that the Q/S values at points A and B are the same and set in sequence, and that the Q/S values at points C and D are the same and set in sequence. Otherwise, a message indicating invalid input is displayed. |
|
Remote Communication Scheduling
The management system or independent power adjustment device sends scheduling commands over the communications port that supports Modbus-TCP or IEC104, without the need of user configuration or operation. The SmartLogger can automatically switch between scheduling modes and send scheduling commands.
Parameter |
Description |
---|---|
As the Remote communication scheduling mode has a higher priority, the SmartLogger automatically changes Reactive power control mode to Remote communication scheduling after receiving a scheduling command from the upper-layer management system. If this parameter is set to Remote communication scheduling, the SmartLogger parses the scheduling command delivered by the upper-layer management system to valid instruction data that can be identified by the devices in the plant and delivers the data to all devices connected to the SmartLogger. |
|
The default value is Disable. If this parameter is set to Enable, the SmartLogger shuts down the device when the communication between the SmartLogger and the scheduling backend is interrupted for a period longer than the set value of Reactive power scheduling timeout threshold for triggering solar inverter shutdown. |
|
The default value is 300. This parameter is used only for shutdown protection for reactive power scheduling when the communication between the SmartLogger and the scheduling backend is abnormal. If the communication is interrupted for a period longer than the set value, it is determined as abnormal. |
|
The default value is Enable. If this parameter is set to Enable, after a reactive power signal timeout occurs, if the reactive power signal recovers, the device automatically starts. |
|
The default value is Disable. If this parameter is set to Enable, the SmartLogger controls the device in the following ways after the communication between the SmartLogger and the scheduling backend is interrupted for a period longer than the set value of Reactive power scheduling timeout threshold for triggering solar inverter power limiting.
|
|
The default value is 300.0. This parameter is used only for reactive power limiting protection when the communication between the SmartLogger and the scheduling backend is abnormal. If the communication is interrupted for a period longer than the set value, reactive power limiting protection is started. |
|
The default value is 0.000. After Limit solar inverter power upon reactive power scheduling timeout is enabled, if the communication between the SmartLogger and the scheduling backend is interrupted for a period longer than the set value of Reactive power scheduling timeout threshold for triggering solar inverter power limiting, the SmartLogger limits the active power of the inverter based on the set value of this parameter. |
|
The default value is 0.000. After Limit solar inverter power upon reactive power scheduling timeout is enabled, if the communication between the SmartLogger and the scheduling backend is interrupted for a period longer than the set value of Reactive power scheduling timeout threshold for triggering solar inverter power limiting, the SmartLogger limits the reactive power of the Smart PCS based on the set value of this parameter. |
Power Factor Closed-Loop Control (Old Policy)
Before setting the parameters, ensure that the power meter is correctly connected to the SmartLogger.
Parameter |
Description |
---|---|
Set this parameter to Power factor closed-loop control (old policy). |
|
Specifies the target value for the adjustment power factor of the power meter. |
|
Specifies the interval for sending adjustment commands by the SmartLogger. |
|
Specifies the adjustment power factor precision. NOTICE:
This parameter is valid only when the power factor of the power meter is greater than 0.9. |
Power Factor Closed-Loop Control
To improve the revenue, a distributed plant needs to reduce or avoid the power factor surcharge by performing distributed reactive power compensation. To enable the function, set the related parameters.
- You are advised to choose to enable smart reactive power compensation.
- Before setting the parameters, ensure that the license for smart reactive power compensation has been loaded on the page.
- Before setting the parameters, ensure that the power meter is correctly connected to the SmartLogger.
Parameter |
Description |
---|---|
Set this parameter to Power factor closed-loop control. |
|
|
|
Set this parameter to Smart meter. |
|
Specifies the target value for the adjustment power factor of the power meter. The target value should be larger than the appraisal value of the PV plant power factor. |
|
Specifies the interval for sending adjustment commands by the SmartLogger. |
|
Specifies the adjustment power factor precision. NOTICE:
This parameter is valid only when the power factor of the power meter is greater than 0.9. |
|
Specifies the delay time for starting the distributed power factor compensation if the current power factor is lower than the target power factor. |
|
Note [1]: If cables are reversely connected to the meter and the NMS can correctly display the real-time data of the meter, it is considered that the NMS supports reverse connection. That is, the NMS reverses the active power, reactive power, power factor, phase A active power, phase B active power, and phase C active power, replaces the total positive active energy and total negative active energy with each other, and replaces the total positive reactive power and total negative reactive power with each other. Note [2]: Meter access direction is set in the meter running parameters. |
When the SmartLogger receives a remote reactive power scheduling command from the plant, it automatically changes Reactive power control mode to Remote communication scheduling. If power factor closed-loop control is required, set Reactive power control mode to Power factor closed-loop control and set the target power factor correctly.
PF-U Characteristic Curve
If the remote reactive power control command is not available, you can configure the characteristic curve as a substitute. The SmartLogger delivers the values configured for the characteristic curve to the inverter or Smart PCS, which then operates according to the configuration. The SmartLogger no longer adjusts the values.
Configure the characteristic curve under instructions from professionals to ensure that the inverter or Smart PCS works properly.
In the PF-U characteristic curve control mode, the inverter or Smart PCS dynamically adjusts the PF at the device port based on the ratio U/Un(%) of the actual grid voltage to the rated grid voltage.
Parameter |
Description |
---|---|
Set this parameter to PF-U characteristic curve. |
|
|
|
When configuring the curve, ensure that the U/Un(%) value of a point is greater than that of the previous point. Otherwise, the "Invalid input" message will be displayed. |
|
Q-P Characteristic Curve
If the remote reactive power control command is not available, you can configure the characteristic curve as a substitute. The SmartLogger delivers the values configured for the characteristic curve to the inverter or Smart PCS, which then operates according to the configuration. The SmartLogger no longer adjusts the values.
Configure the characteristic curve under instructions from professionals to ensure that the inverter or Smart PCS works properly.
In the control mode of the Q-P characteristic curve, the inverter or Smart PCS adjusts the ratio Q/Pn of the output reactive power to the rated power based on the ratio P/Pn of the current active power to the rated power.
Parameter |
Description |
---|---|
Set this parameter to Q-P characteristic curve. |
|
Specifies the change interval of the reactive power at the grid-connection point. |
|
|
|
When configuring the curve, ensure that the P/Pn value of a point is greater than that of the previous point. Otherwise, the "Invalid input" message will be displayed. |
|
- No Output
- DI Reactive Scheduling
- Reactive Power Fix Control
- Power Factor Fix Control
- Q-U Characteristic Curve
- cosφ-P/Pn Characteristic Curve
- Q-U Hysteresis Curve (CEI0-16)
- Remote Communication Scheduling
- Power Factor Closed-Loop Control (Old Policy)
- Power Factor Closed-Loop Control
- PF-U Characteristic Curve
- Q-P Characteristic Curve