Setting GOOSE Communications Parameters
The GOOSE parameters can be configured only for V300R023C00 and later versions.
Choose Submit.
, set the GOOSE parameters, and clickBasic Parameters
Parameter |
Description |
Remarks |
---|---|---|
The default value is Disable.
|
- |
|
The default value is Disable.
|
This parameter is displayed when Connection is set to Enable. |
|
The default value is Disable.
|
||
WAN or SPF is supported. The default value is WAN. This parameter specifies the type of the network port used by the SmartLogger to send and receive GOOSE messages. Set this parameter based on the actual networking scenario. |
||
The default value is Disable.
|
||
Note [1]: The GOOSE fast scheduling function is mutually exclusive with the fast scheduling function of the Modbus TCP interface. The fast scheduling function of only one protocol takes effect at a time. |
Configuration File Import/Export
- This parameter is displayed when Connection is set to Enable.
- You can contact the vendor to obtain the CID files of the SmartLogger and the peer controller. Compress the CID files of the SmartLogger and the peer controller into a .zip configuration package, and click Import Config. Import the configuration package. After the configuration is parsed successfully, the Device name, Controller type, Controller name, Configuration status, and Last import time are displayed. For details about GOOSE interconnection and interfaces, see the SmartLogger IEC61850 GOOSE Protocol Interface Description.If the configuration file is imported and parsed successfully, the configuration status is Configured. If the configuration file import fails, contact the vendor of the peer controller to obtain the correct CID file.
Message Indicating Failed Configuration
Description
Suggestion
Import failed. The configuration file is incomplete.
The CID file of the local or peer device is missing.
Contact the vendor of the peer controller to obtain the correct CID file.
Import failed. The configuration file is not for this device.
The file does not match the vendor or the device type.
Import failed. Unable to parse the configuration file.
The CID file format is incorrect. Parsing failed or no matching signal is found.
- Click Export Config. to obtain the ICD file of the current SmartLogger version. The CID file is exported at the same time if it has been imported successfully.