Commissioning Using Deployment Wizard (V300R023C00)
Context
The deployment wizard allows you to set basic SmartLogger parameters, connect Huawei devices, power meters, and EMIs, configure battery control, Huawei NMS, and third-party NMS, and implement interworking with third-party devices. In utility-scale storage-only scenarios and microgrid scenarios, the insulation fault detection function of the Smart PCS is added to improve system safety and reduce costs.
After the SmartModule communicates with the SmartLogger properly, the SmartLogger automatically identifies the SmartModule. The device name of the SmartModule is Module(M1), and the corresponding port is M1.port.
Prerequisites
In utility-scale storage-only scenarios and microgrid scenarios, the insulation fault detection function of the Smart PCS supports only the following Huawei devices.
Device Name |
Device Model |
---|---|
Smart String ESS |
LUNA2000-2.0MWH-4H1, LUNA2000-2.0MWH-2H1, LUNA2000-2.0MWH-2H0, LUNA2000-2.0MWH-1H1, LUNA2000-2.0MWH-1H0, LUNA2000-1.0MWH-1H1, LUNA2000-200KTL-H1, and LUNA2000-200KTL-H0 |
STS |
STS-6000K-H1, STS-3000K-H1, and JUPITER-9000K-H0 |
SACU |
SmartACU2000D-D-03 |
Procedure
During parameter setting, click Previous, Next, or Skip as required. For details, see Help on the page.
- Click Deployment Wizard and set basic parameters.
- Set basic parameters.Figure 6-18 Setting basic parameters
- Select a communication mode based on site requirements.
- Set basic parameters.
- Connect Huawei devices.
- Click Search for Device to check the cable connections and allocate addresses.Figure 6-19 Searching for devices
- During the process of Search for Device, do not perform upgrade operations (such as upgrading through the app, management system, or WebUI).
- When you click Search for Device, cable connections (DC and AC) will be checked before device search (not applicable to third-party devices), and device addresses will be automatically allocated.
- After the cable connection check and device search are complete, if a cable connection alarm is generated, you can click the alarm icon
to view the corresponding alarm information.
- If an alarm is generated when the cable connection check fails, click the alarm icon
to view the alarm cause and handling suggestions. After the fault is rectified, check the cable connections again.
- After the cable connection check and device search are complete, click
to view the corresponding topology information.
- After a device is added or deleted, you need to click Search for Device again in Deployment Wizard. Otherwise, the system topology will not be updated.
- Set parameters such as Microgrid compatibility and Grid Code.
Table 6-3 Parameter settings after device search (for versions earlier than SmartLogger V300R023C10)
Parameter
Description
Running under Grid connection state
Set this parameter only for the PCS, but not for the SUN2000.
- In the on-grid scenario, set this parameter to On-grid(PQ).
- In the off-grid scenario, set this parameter to Off-grid(VSG).
Microgrid compatibility
- In the on-grid scenario, set this parameter to Disable.
- In the off-grid scenario, set this parameter to Enable.
Grid Code
Set this parameter based on the grid code of the country or region where the devices are used.
For PCSs on the same DC bus, ensure that the settings of Running under Grid connection state and Microgrid compatibility are the same.
Table 6-4 Parameter settings after device search (SmartLogger V300R023C10 and later versions)Parameter
Description
Scenario under Arrays Operation Scenario
- In the on-grid scenario, set this parameter to On-grid.
- In the off-grid scenario, set this parameter to Off-grid.
- In the on/off-grid switching scenario, set this parameter to On/Off-grid.
Grid Code
Set this parameter based on the grid code of the country or region where the devices are used.
Working mode under Parameter Configuration
- Set this parameter to PQ for the current source mode.
- Set this parameter to VSG for the voltage source mode.
Microgrid compatibility under Parameter Configuration
- In the on-grid scenario, set this parameter to Disable.
- In the off-grid scenario, set this parameter to Enable.
Active Power Baseline (kW) under Parameter Configuration
Set the lower limit of the maximum apparent power, which is also used as the baseline for active power scheduling.
Apparent Power Baseline (kVA) under Parameter Configuration
Set the upper limit of the maximum active power, which is also used as the baseline for reactive power scheduling.
Maximum Overload Active Power (kW) under Parameter Configuration
Set the maximum overload active power for grid forming.
Maximum Overload Apparent Power (kVA) under Parameter Configuration
Set the maximum overload apparent power for grid forming.
For PCSs on the same DC bus, ensure that the settings of Scenario under Arrays Operation Scenario and Microgrid compatibility are the same.
- Click Search for Device to check the cable connections and allocate addresses.
- Connect to power meters.Figure 6-20 Setting meter parameters
- Connect to EMIs.Figure 6-21 Setting EMI parameters
- Set battery control. This step is required only for the energy storage scenarios.
- Set the battery control working mode.Figure 6-22 Working modeTable 6-5 Battery control working modes
Working Mode
Mode Description
No control
The SmartLogger directly delivers the external scheduling power limit. No other power scheduling control is performed. The power is automatically controlled by the device.
Maximum self-consumption
- This mode applies to areas where the electricity price is high, or areas where the FIT subsidy is low or unavailable. The PV+ESS system generates sufficient PV power for loads and uses the surplus PV power to charge the ESS (if the PV power is insufficient for loads, the TOU mode is recommended).
- PV power is preferentially supplied to loads, and the surplus power is used to charge the ESS. If the ESS is fully charged or is being charged at full power, the surplus power is fed to the grid. When PV power is insufficient or no PV power can be generated at night, the ESS discharges power to loads. This improves the self-consumption rate and energy self-sufficiency rate, and reduces electricity costs. The grid cannot charge the ESS but can supply power to loads.
- The SmartLogger performs ESS scheduling based on the external scheduling power limit and the preceding policies.
Fully fed to grid
- This parameter applies only to distributed scenarios.
- This mode maximizes the PV energy fed to the grid. When the PV output power in the daytime is greater than the maximum output capacity of the inverter, the surplus PV power is used to charge the ESS. When the PV output power is less than the maximum output capacity of the inverter, the ESS discharges energy to the inverter to maximize the energy fed from the inverter to the grid. The grid cannot charge the ESS.
- The SmartLogger directly delivers the external scheduling power limit.
NOTE:If the CMU is connected, the Fully fed to grid working mode is not displayed.
TOU
- It is applicable to the PV+ESS system and ESS-only system where peak to valley electricity prices are different and power meters are available.
- You can manually set the charge and discharge time segments. For example, if you set the low electricity price period at night as the charge time, the system charges the batteries at the maximum power during the charge time. If you set the high electricity price period as the discharge time, batteries can discharge only during the discharge time based on the actual load power, reducing electricity costs.
- Click Add to set the charge and discharge time segments. A maximum of 14 time segments can be set. During the charge time, the grid can charge the batteries. During the discharge time, the batteries can supply power to the loads. In other time segments, the batteries do not discharge. The PV system and grid supply power to loads, and the PV system can charge the batteries.
- In some countries, the grid is not allowed to charge batteries. In such case, this mode cannot be used.
- The SmartLogger performs battery scheduling based on the external scheduling power limit and the preceding policies.
TOU (fixed power)[1]
- It is applicable to the PV+ESS system and ESS-only system where peak to valley electricity prices are different and power meters are unavailable.
- You can manually set the charge and discharge time segments. For example, if you set the low electricity price period at night as the charge time, the system charges the batteries at the fixed power during the charge time. If you set the high electricity price period as the discharge time, batteries can discharge only during the discharge time at the fixed power, reducing electricity costs.
- Click Add to set the charge and discharge time segments. A maximum of 14 time segments can be set. During the charge time, the grid can charge the batteries. During the discharge time, the batteries can supply power to the loads. In other time segments, the batteries do not discharge and are not charged.
- In some countries, the grid is not allowed to charge batteries. In such case, this mode cannot be used.
- The SmartLogger performs battery scheduling based on the external scheduling power limit and the preceding policies.
Charge/Discharge based on grid dispatch
- This mode applies to utility-scale plant scheduling scenarios where a third-party controller delivers active power scheduling commands.
- The purpose of scheduled discharge is to meet the active power scheduling target value at the grid access point. PV energy is preferred. If the generated PV energy is insufficient, the batteries discharge and the energy is fed to the grid based on the active power scheduling target value. If the generated PV energy is sufficient, the energy is fed to the grid based on the active power scheduling target value, and the surplus PV energy is used to charge the batteries.
- The purpose of scheduled charge is to meet the active power scheduling target value at the grid access point. If the battery charge power is insufficient or the Smart PCS limits the power, the grid charges the batteries with the maximum capability. If the batteries are not fully charged when the scheduling target value is met, the PV power is used to charge the batteries.
Custom[2]
- This mode applies to utility-scale plant (with ESSs) scheduling scenarios. Customers can control the battery discharge power.
- Non-discharge period: The batteries cannot discharge and can be charged based on the scheduling command.
- Discharge period: If Adaptive discharge power is enabled, the control logic is the same as that for scheduled charge and discharge. The battery charge and discharge power is determined by the upper-layer scheduling command. If Adaptive discharge power is disabled, the battery discharge power is fixed to the reference value set by the customer. In this case, the upper-layer scheduling command controls only the PV inverters but not the batteries.
Note [1]: You can set this parameter in SmartLogger V300R023C00SPC150 and later versions.
Note [2]: You can set this parameter in SmartLogger V300R023C00SPC120 and later versions.
Table 6-6 Running parameters in each battery control working modeWorking Mode
Parameter
Description
Maximum self-consumption
Active power threshold of grid during battery discharge
Set the grid power threshold at the grid connection point for loads when the load power is greater than the PV power.
Adjustment deadband
Set the precision of the grid power at the grid connection point. This parameter affects the power value range at the grid connection point. If the actual grid power threshold at the grid connection point is within this range, i.e. [Maximum grid power during battery discharge – Adjustment deadband, Maximum grid power during battery discharge + Adjustment deadband], the grid power requirement at the grid connection point is met.
Adaptive adjustment parameters[1]
Set the adjustment period and step parameters for raising the inverter power.
- Enable: The adjustment period and step set in the SmartLogger are used. Generally, the adjustment period and step are calculated based on the number of devices connected to the port and device specifications.
- Disable: Use this value based on site requirements.
Adjustment period[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, battery control is performed based on the preset period.
PV adjustment step[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, the PV rise step for PV+ESS equalization is the preset value.
TOU
Preferred use of surplus PV power
- Charge: When the PV power is greater than the load power, the surplus PV energy is used to charge the batteries. After the maximum charge power is reached or the batteries are fully charged, the surplus PV energy is fed to the grid.
- Fed to grid: When the PV power is greater than the load power, the surplus PV energy is preferentially fed to the grid. When the maximum output power of the device is reached, the surplus energy is used to charge the batteries. This setting is applicable to the scenario where the FIT is higher than the electricity price. The grid cannot charge the batteries.
Maximum power for charging batteries from grid
Set the maximum power at which the grid charges the batteries.
Active power threshold of grid during battery discharge
Set the grid power threshold at the grid connection point for loads when the load power is greater than the PV power.
Adjustment deadband
Set the precision of the grid power at the grid connection point. This parameter affects the power value range at the grid connection point. If the actual grid power threshold at the grid connection point is within this range, i.e. [Maximum grid power during battery discharge – Adjustment deadband, Maximum grid power during battery discharge + Adjustment deadband], the grid power requirement at the grid connection point is met.
Adaptive adjustment parameters[1]
Set the adjustment period and step parameters for raising the inverter power.
- Enable: The adjustment period and step set in the SmartLogger are used. Generally, the adjustment period and step are calculated based on the number of devices connected to the port and device specifications.
- Disable: Use this value based on site requirements.
Adjustment period[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, battery control is performed based on the preset period.
PV adjustment step[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, the PV rise step for PV+ESS equalization is the preset value.
Start time
Set the start time and end time of charge and discharge. A maximum of 14 time segments can be set. You can set a cycle by week by clicking the buttons corresponding to Mon. through Sun. in the Repeat box. The buttons are blue by default, indicating being selected. After you click it, the button turns gray.
End time
Charge/Discharge
Repeat
TOU (fixed power)
Start time
Set the start time, end time, and power of charge and discharge. A maximum of 14 time segments can be set. You can set a cycle by week by clicking the buttons corresponding to Mon. through Sun. in the Repeat box. The buttons are blue by default, indicating being selected. After you click it, the button turns gray.
End time
Charge/Discharge
Charge/Discharge power (kW)
Repeat
Charge/Discharge based on grid dispatch
Adaptive adjustment parameters[1]
Set the adjustment period and step parameters for raising the inverter power.
- Enable: The adjustment period and step set in the SmartLogger are used. Generally, the adjustment period and step are calculated based on the number of devices connected to the port and device specifications.
- Disable: Use this value based on site requirements.
Adjustment period[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, battery control is performed based on the preset period.
PV adjustment step[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, the PV rise step for PV+ESS equalization is the preset value.
Array end-of-charge SOC
The default value is 100%. The default value is recommended. Set this parameter as required.
Array end-of-discharge SOC
The default value is 5%. The default value is recommended. Set this parameter as required.
Array end-of-charge/discharge SOC derating
The default value is Disable. The default value is recommended. Set this parameter as required. After this parameter is enabled, the SmartLogger will be derated according to a certain slope to prevent sudden power changes of arrays at the cut-off SOC point.
Control charge/discharge time window
The default value is Disable. The default value is recommended. Set this parameter as required. You can set the time segment for charge forbidden, discharge forbidden, charge, and discharge only after the control charge/discharge time window is enabled.
Start time
Set the start time, end time, and power of charge forbidden, discharge forbidden, charge, and discharge. A maximum of 14 time segments can be set. You can set a cycle by week by clicking the buttons corresponding to Mon. through Sun. in the Repeat box. The buttons are blue by default, indicating being selected. After you click it, the button turns gray.
End time
Charge/Discharge
Charge/Discharge power (kW)
Repeat
Protection against communication disconnection
The default value is Disable. The default value is recommended. Set this parameter as required.
NOTE:In the utility-scale ESS low-voltage coupling scenario, the PV+ESS capacity exceeds the transformer station capacity. You are advised to set this parameter to Enable.
Custom
ESS discharge start time
Set the start time of battery discharge. During the period from the start time to the end time, the batteries can be charged and can discharge. Beyond the period, the batteries cannot discharge and can only be charged.
ESS discharge end time
Set the end time of battery discharge. During the period from the start time to the end time, the batteries can be charged and can discharge. Beyond the period, the batteries cannot discharge and can only be charged.
Adaptive discharge power
- Enable: PV power supply is preferred. If the PV power is insufficient, the batteries supply power to loads; if the PV power is sufficient, the system outputs at the target value and the surplus PV power is used to charge the batteries.
- Disable: Batteries discharge based on the discharge power set on the GUI.
Reference discharge power
Set the battery discharge power during the discharge period.
Adaptive adjustment parameters[1]
Set the adjustment period and step parameters for raising the inverter power.
- Enable: The adjustment period and step set in the SmartLogger are used. Generally, the adjustment period and step are calculated based on the number of devices connected to the port and device specifications.
- Disable: Use this value based on site requirements.
Adjustment period[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, battery control is performed based on the preset period.
PV adjustment step[1]
This parameter is displayed after Adaptive adjustment parameters is set to Disable. You can set this parameter based on site requirements. In this case, the PV rise step for PV+ESS equalization is the preset value.
Note [1]: This parameter is added in SmartLogger V300R023C00SPC120 and later versions. This parameter is displayed and needs to be set only when the Smart PCS is connected.
- Set the automatic calibration functions.
Parameter
Description
Automatic SOC calibration
- If this parameter is set to Enable, automatic charge and discharge calibration is allowed for battery racks. During calibration, the cut-off SOC settings will be ineffective and the response of the charge and discharge power may be impacted temporarily.
- If this parameter is set to Disable, automatic charge and discharge calibration is not allowed for battery racks.
Automatic SOC calibration interval[1]
Set the automatic SOC calibration interval. This parameter is displayed when Automatic SOH calibration is set Enable.
If the battery SOC stays in the range of 10% to 99% most of the time, for example, in the microgrid scenario, the recommended online calibration interval is less than or equal to 7 days.
If the battery SOC stays in the range of 40% to 60% most of the time, for example, in the frequency regulation scenario, the recommended online calibration interval is less than or equal to 30 days.
If the battery SOC stays below 10% or at 100% most of the time, for example, in the peak shaving scenario, the recommended online calibration interval is less than or equal to 180 days.
Automatic SOH calibration
- If this parameter is set to Enable, the ESS automatically calibrates the SOH precision and fully charges and discharges each battery rack in turn.
- If this parameter is set to Disable, automatic SOH calibration is not allowed for battery racks.
Note [1]: You can set this parameter in SmartLogger V300R023C00SPCXXX and later versions.
- Set PCS insulation resistance detection.If a dialog box You are advised to change the insulation resistance detection time to the optimal time (XX:XX) is displayed, you are advised to click Confirm and set Detection start time to the optimal time. This policy applies only to the C&I scenario and is supported in SmartLogger V300R023C00SPC172 and later versions.Table 6-7 Setting parameters related to PCS insulation resistance detection
Parameter
Description
Detection start time[1]
It indicates the time when the PCS insulation resistance detection function is enabled. The default value is 02:00.
Note [1]: You can set this parameter in SmartLogger V300R023C00SPC153 and later versions.
- Set the battery control working mode.
- Connect to the Huawei NMS.Figure 6-23 Huawei NMS
- For third-party NMS access, select a protocol based on the actual third-party NMS protocol.Figure 6-24 Third-party NMS
- Connect to third-party devices.Figure 6-25 Third-party devices
- Set Array startup/shutdown based on the site requirements. The configuration is complete.Figure 6-26 Completing the configuration