This document describes the SmartLogger3000 and SmartModule1000A01 in terms of installation, electrical connections, system operation, maintenance, and troubleshooting. BOM number: 02312SCU, 02312SCU-001, 02312SCU-002, 02312SCU-003, 02312SCU-004, 02312SCU-005, 02312SCU-006, 02312SCU-007, 02312SCU-008, 02312SCU-009, 02312SCU-010, 02312SGF, 02312SGG, 02312SGK and 02312SGJ.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Setting EMI Parameters

Setting EMI Parameters

Setting Modbus-RTU EMI Parameters

Procedure

  1. Set access parameters and click Add Devices.

    Figure 6-27 Setting access parameters

    Parameter

    Description

    Device Type

    Set this parameter to EMI.

    Connection mode

    Set this parameter to Modbus-RTU.

    Port number

    Set this parameter to the serial number of the COM port connected to the EMI.

    Address

    Set this parameter to the communication address of the EMI.

  2. Set running parameters and click Submit.

    Figure 6-28 Setting running parameters
    • If the model of the connected EMI is displayed in the EMI model drop-down list box, set parameters as follows.

    Parameter

    Description

    EMI model

    Set this parameter to the model of the connected EMI.

    Synchronize Environment Data

    You are advised to retain the default value Disable.

    NOTE:

    When this parameter is set to Enable, the SmartLogger transmits the wind speed and direction data to the solar inverter in a PV plant with the tracking system.

    Master/Slave

    When the SmartLogger connects to multiple EMIs, set one of them to master mode. The solar inverter performance data displayed is the data of the EMI in master mode.

    • If the connected EMI is a split EMI that supports Modbus-RTU, set parameters as follows.

    Parameter

    Description

    EMI model

    Set this parameter to Sensor(ADAM).

    Synchronize Environment Data

    You are advised to retain the default value Disable.

    NOTE:

    When this parameter is set to Enable, the SmartLogger transmits the wind speed and direction data to the solar inverter in a PV plant with the tracking system.

    Master/Slave

    When the SmartLogger connects to multiple EMIs, set one of them to master mode. The solar inverter performance data displayed is the data of the EMI in master mode.

    Read function code

    Set this parameter to Read holding register 03H or Read holding register 04H based on the protocol adopted by the vendor.

    Data reporting mode

    Set this parameter to Integer or Floating point based on the protocol adopted by the vendor.

    Word ordering

    Set this parameter to Big endian or Little endian based on the protocol adopted by the vendor.

    Read mode

    The value can be Multiple read or Single read.

    Start address

    If Read mode is set to Multiple read, set the start address for reading.

    End address

    If Read mode is set to Multiple read, set the end address for reading.

    Signal parameters

    NOTE:

    Signal parameters include Signal Name, Signal address, Lower Thres., Upper Thres., Spec, Start (mV/mA), End (mV/mA), and Unit.

    Set these parameters based on the vendor protocol.

    NOTE:

    If the EMI can collect a signal, set Signal address for the signal to the corresponding register address. If the EMI cannot collect a signal, set Signal address for the signal to 65535.

    • If the connected EMI is of another model, set parameters as follows.

    Parameter

    Description

    EMI model

    Set this parameter to Other.

    Synchronize Environment Data

    You are advised to retain the default value Disable.

    NOTE:

    When this parameter is set to Enable, the SmartLogger transmits the wind speed and direction data to the solar inverter in a PV plant with the tracking system.

    Master/Slave

    When the SmartLogger connects to multiple EMIs, set one of them to master mode. The solar inverter performance data displayed is the data of the EMI in master mode.

    Read function code

    Set this parameter to Read holding register 03H or Read holding register 04H based on the protocol adopted by the vendor.

    Data reporting mode

    Set this parameter to Integer or Floating point based on the protocol adopted by the vendor.

    Word ordering

    Set this parameter to Big endian or Little endian based on the protocol adopted by the vendor.

    Read mode

    The value can be Multiple read or Single read.

    Start address

    If Read mode is set to Multiple read, set the start address for reading.

    End address

    If Read mode is set to Multiple read, set the end address for reading.

    Signal parameters

    NOTE:

    Signal parameters include Signal Name, Signal address, Gain, Offset, and Unit.

    Set these parameters based on the vendor protocol.

    NOTE:

    If the EMI can collect a signal, set Signal address for the signal to the corresponding register address. If the EMI cannot collect a signal, set Signal address for the signal to 65535.

Setting AI EMI Parameters

Procedure

  1. Set access parameters and click Add Devices.

    Figure 6-29 Setting access parameters

    Parameter

    Description

    Device Type

    Set this parameter to EMI.

    Connection mode

    Set this parameter to AI.

    Address

    Set this parameter to the communication address of the EMI.

  2. Set running parameters and click Submit.

    Figure 6-30 Setting running parameters

    Parameter

    Description

    Synchronize Environment Data

    You are advised to retain the default value Disable.

    NOTE:

    When this parameter is set to Enable, the SmartLogger transmits the wind speed and direction data to the solar inverter in a PV plant with the tracking system.

    Master/Slave

    When the SmartLogger connects to multiple EMIs, set one of them to master mode. The solar inverter performance data displayed is the data of the EMI in master mode.

    Signal parameters

    NOTE:

    Signal parameters include Signal Name, Port number, Lower Thres., Upper Thres., Start (V/mA), End (V/mA), and Unit.

    Set these parameters as required.

    NOTE:

    When you need to change the configured port number, set Port number to No first, then to the required port number.

  3. If Port number is set to the number of the connected PT port, click PT T Correction to correct the temperature.