Setting IEC103 Device Parameters
Description
An IEC103 device supports two data transmission modes:
- Transparent transmission mode: When connecting to the management system, the SmartLogger transparently transmits the IEC103 device information to the management system. The SmartLogger does not parse the IEC103 device data.
- Parsing mode: The IEC103 device is connected to the SmartLogger, and the SmartLogger parses the IEC103 device data.
Transparent Transmission Mode
- Set IEC103 parameters and click Submit.Figure 6-57 Setting IEC103 parameters
Parameter
Description
IEC103 port No. Set this parameter based on the COM port connected to the device.
IEC103 address Set this parameter to the IEC103 device address.
IEC103 IP Set this parameter to the IP address of the management system.
- Choose Data forwarding is set to Enable. and check that
- If Data forwarding is set to Enable, the SmartLogger transparently transmits information about unconnected devices to the management system without parsing device data.
- If Data forwarding is set to Disable, the SmartLogger does not transmit information about unconnected devices to the management system.
Parsing Mode
The SmartLogger can connect to third-party devices that support IEC103, such as the relay protection or monitoring device like the transformer substation. The protocol information points vary depending on vendors. Therefore, you need to obtain a protocol information file in .cfg format from Huawei and import the file into the SmartLogger for successfully connecting to a custom device.
The supported device types are IEC103 device 1 to IEC103 device 5. The corresponding configuration file names are iec103_equip_custom_1.cfg to iec103_equip_custom_5.cfg. Multiple devices of the same type can be connected.
- Configure a protocol information point file in .cfg format and import the file to the SmartLogger.Figure 6-58 Importing configuration
- Set access parameters and click Add Devices.Figure 6-59 Setting access parameters
Parameter
Description
Device Type The value can be IEC103 Device 1 to IEC103 Device 5.
Select a value based on the configuration file. For example, if iec103_equip_custom_1.cfg needs to be imported, select IEC103 Device 1.
Port number Set this parameter to the COM port connected to the IEC103 device.
Address Set this parameter to the communication address of the IEC103 device.
- Set device monitoring parameters and click Submit.Figure 6-60 Device monitoring
Tab
Function
Description
Running Info. View the running information about the IEC103 device.
N/A
Teleindication View the device status, such as the switch status.
N/A
Telemetering View the real-time analog data of the device, such as the voltage.
N/A
Telecontrol Set the status control parameters, such as the parameters for turning on or off switches.
Set the parameters on the tab page as required.
Teleadjust Set analog parameters, for example, set voltage protection parameters.
Set the parameters on the tab page as required.