Upgrading the Device Firmware Version
Context
You can upgrade the software of the SmartLogger, inverter, Smart PCS, Smart String ESS, MBUS module, or PID module on the WebUI.
Procedure
- Perform an upgrade.Figure 7-1 Upgrade
- The Stop Upgrade function applies only to the devices waiting to be upgraded.
- If the active power control mode is set to Grid connection with limited power or Remote communication scheduling, and the reactive power control mode is set to Power factor closed-loop control or the working mode of Battery Control is enabled, you are advised to upgrade software when inverters and Smart PCSs are disconnected from the grid. Otherwise, power control may be abnormal or the upgrade may fail.