Choose , set running parameters, and click Submit.
Running Parameters
Parameter
|
Description
|
Enable delayed update
|
- The default value is Enable. When delayed upgrade is set, after the upgrade package is uploaded, the ESU will perform the upgrade automatically when the SOC is greater than or equal to 30%, the rack voltage is greater than or equal to 400 V, and the ESC and ESM communicate properly.
- If this parameter is set to Disable, the upgrade can be performed immediately. The upgrade may fail if the upgrade conditions are not met.
|
Delete invalid battery packs
|
Delete battery packs that are not connected. This function is used when replacing battery packs.
|
Battery pack shutdown delay
|
After this parameter is set, the system can still monitor the battery for a period of time after power-off.
|
Shutdown due to communication interruption between the rack controller and PCS
|
- The default value is Disable.
- If this parameter is set to Enable, the ESS shuts down when the communication between the PCS and the rack controller is interrupted.
|