Preparing Cables
Type |
Recommended Cable Specifications |
---|---|
PE cable |
Outdoor copper-core cable with a cross-sectional area of 4–6 mm2 or 12–10 AWG |
RS485 communications cable |
Two-core or multi-core outdoor shielded cable with a cross-sectional area of 0.2–2.5 mm2 or 24–14 AWG |
(Optional) MBUS cable |
Delivered with the SmartLogger, 1.5 m long |
DI signal cable |
Two-core or multiple-core cable with a cross-sectional area of 0.2–1.5 mm2 or 24–16 AWG |
Output power cable |
|
AI signal cable |
|
DO signal cable |
|
Network cable |
Delivered with the SmartLogger, 2.2 m long. If the delivered network cable is too short, you are advised to prepare a network cable of Cat 5e or higher specifications and shielded RJ45 connectors. |
(Optional) 24 V input power cable |
Two-core cable with a cross-sectional area of 0.2–1.5 mm2 or 24–16 AWG |