This document describes the SmartLogger3000 and SmartModule1000A01 in terms of installation, electrical connections, system operation, maintenance, and troubleshooting. BOM number: 02312SCU, 02312SCU-001, 02312SCU-002, 02312SCU-003, 02312SCU-004, 02312SCU-005, 02312SCU-006, 02312SCU-007, 02312SCU-008, 02312SCU-009, 02312SCU-010, 02312SGF, 02312SGG, 02312SGK and 02312SGJ.

Rate and give feedback:
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Preparing Cables

Preparing Cables

Type

Recommended Cable Specifications

PE cable

Outdoor copper-core cable with a cross-sectional area of 4–6 mm2 or 12–10 AWG

Network cable

The cable is delivered with the SmartModule and is 0.35 m long. If the delivered network cable is too short, you are advised to prepare a network cable of Cat 5e or higher specifications and shielded RJ45 connectors.

12 V power input cable

The cable is delivered with the SmartModule and is 0.5 m long.

RS485 communications cable

Two-core or multiple-core cable with a cross-sectional area of 0.2–2.5 mm2 or 24–14 AWG

DI signal cable

Two-core or multiple-core cable with a cross-sectional area of 0.2–1.5 mm2 or 24–16 AWG

Output power cable

AI signal cable

PT signal cable

For details about the cables and cable connection operations, see the documents delivered with the PT100/PT1000.

(Optional) 24 V power input cable

Two-core cable with a cross-sectional area of 0.2–1.5 mm2 or 24–16 AWG