Installing a PCIe Riser Module
Procedure
- Power off the server.
For details, see Power-Off Procedure.
- Remove the power cables from the PSUs.
For details, see Removing PSU Cables.
- Remove the server.
For details, see Removing the Server.
- Place the server on the ESD workstation.
- Remove the chassis cover.
For details, see Removing the Chassis Cover.
- Determine the position of the PCIe riser module.
- Remove the filler panel.
Perform this operation only when a filler panel is installed.
Figure 6-172 Removing a filler panel from I/O module 1 (example)Figure 6-173 Removing the filler panel from I/O module 3 (example) - Take the spare part out of its ESD bag.
- Install the PCIe riser modules.
- Install the PCIe riser module in I/O module 1 or 2.
- Install the PCIe card on the PCIe riser module.
For details, see Installing a PCIe Card.
- Place the PCIe riser module into the slot in the chassis, and tighten the screws.
Figure 6-174 Installing the PCIe riser module in I/O module 2 (example) - Install the PCIe card on the PCIe riser module.
- Install the PCIe riser module in I/O module 3.
- Install the PCIe riser module base. See Figure 6-175.
- Connect the power cable to the riser card. See Figure 6-176.
- Install the PCIe card on the PCIe riser module.
For details, see Installing a PCIe Card.
- Install the PCIe riser module. See Figure 6-177.
- Install the PCIe riser module in I/O module 1 or 2.
- Install the chassis cover.
For details, see Installing the Chassis Cover.
- Install the server.
For details, see Installing a Server.
- Connect the power cables to the PSUs.
For details, see Connecting PSU Cables.
- Power on the server.
For details, see Power-On Procedure.
- Log in to the iBMC WebUI, and check whether the new component is normal.
For details, see the Atlas 800 Inference Server iBMC User Guide (Model 3010).