Installing the TPM/TCM
Procedure
- Power off the server.
For details, see Power-Off Procedure.
- Remove the power cables from the PSUs.
For details, see Removing PSU Cables.
- Remove the server.
For details, see Removing the Server.
- Place the server on the ESD workstation.
- Remove the chassis cover.
For details, see Removing the Chassis Cover.
- Determine whether a built-in drive module is configured.
- Remove the built-in drive module.
For details, see Removing the Built-in Drive Module.
- Take the spare part out of its ESD bag.
- Determine the position of the TPM/TCM.Figure 8-111 Position of the TPM/TCM
- Install the TPM/TCM.
- Insert the TPM/TCM vertically into the connector on the mainboard. See (1) in Figure 8-112.
- Tighten the screw to secure the TPM/TCM. See (2) in Figure 8-112.
- Determine whether a built-in drive module is configured.
- Install the built-in drive module.
For details, see Installing the Built-in Drive Module.
- Install the chassis cover.
For details, see Installing the Chassis Cover.
- Install the server.
For details, see Installing a Server.
- Connect the power cables to the PSUs.
For details, see Connecting PSU Cables.
- Power on the server.
For details, see Power-On Procedure.
- Log in to the iBMC WebUI, and check whether the new component is normal.
For details, see Atlas 800 Inference Server iBMC User Guide (Model 3010).
- Enable the TPM/TCM function.
- To enable the TPM function, perform the following steps:
- Access the BIOS interface.
For details, see Huawei Atlas Server Purley Platform BIOS Parameter Reference.
- Select Security.
- Select TPM Operation and press Enter.
- Select Enable.
- Press F10.
The Save Changes&Exit dialog box is displayed.
- Click Yes and press Enter.
The settings are saved.
- Restart the server.
The TPM settings take effect after the server is restarted.
- Access the BIOS interface.
- To enable the TCM function, perform the following steps:
- Access the BIOS interface.
For details, see Huawei Atlas Server Purley Platform BIOS Parameter Reference.
- Select Security.
- Select Trusted Platform Support and press Enter.
- Select Yes.
- Select TCM Enabled&Activated and press Enter.
- Select Yes.
- Press F10.
The Save Changes&Exit dialog box is displayed.
- Click Yes and press Enter.
The settings are saved.
- Restart the server.
The TCM settings take effect after the server is restarted.
- Access the BIOS interface.
- To enable the TPM function, perform the following steps: