Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document. Note: Even the most advanced machine translation cannot match the quality of professional translators. Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Installing a Common Dehydrating Breather

Installing a Common Dehydrating Breather

  1. Remove the flange cover from the position to install the dehydrating breather.
  2. Secure the dehydrating breather.

    There is a sealing washer between the flange cover and dehydrating breather. When tightening the bolt, ensure that the sealing washer is 1/4 compressed in height.

    Figure 5-11 Securing the dehydrating breather

  3. Remove the end cover from the dehydrating breather.
  4. Add transformer oil to the cover of the dehydrating breather and reinstall the cover.

    Figure 5-12 Securing the end cover