Routine Maintenance
No. |
Check Item |
Acceptance Criteria |
Check Method and Troubleshooting |
Recommended Check Interval |
---|---|---|---|---|
1 |
Equipment room environment |
|
|
Monthly |
2 |
Rodent-proof |
Rodent-proof measures are taken in the equipment room, such as rat guard and mouse trap. |
|
Monthly |
3 |
Equipment room's firefighting system |
A fire alarm system and fire extinguishers have been installed in the battery equipment room. |
|
Monthly |
4 |
Installation position |
There is no air exhaust vent or refrigerant copper pipe of the air conditioner placed above the lithium battery cabinet, and no other water leakage risks exist. |
|
Monthly |
5 |
Ambient temperature |
Actual temperature: ______°C (Allowed temperature: 0°C to 40°C; recommended temperature: 20°C to 25°C) |
|
Monthly |
6 |
Ambient humidity |
Actual humidity: ______% (5–95% RH, non-condensing) |
|
Monthly |
No. |
Check Item |
Acceptance Criteria |
Check Method and Troubleshooting |
Recommended Check Interval |
---|---|---|---|---|
1 |
Cabinet appearance |
The cabinet is free from dust (on air filters and fans), rust, and deformation. |
|
Monthly |
2 |
Battery appearance |
|
|
Monthly |
3 |
Cabinet cable hole protection |
The cable holes of the lithium battery cabinet have been sealed using the standard sealing plates or glands, and rodent-proof measures are taken. |
|
Monthly |
4 |
Cabinet air exhaust vent |
The upper air exhaust vent of the lithium battery cabinet is not blocked. |
|
Monthly |
5 |
Metal scraps in the cabinet |
There is no copper scrap or other conductive foreign matter in the cabinet. |
|
Monthly |
6 |
Fire extinguisher cylinder status |
The pointer of the pressure gauge on the front door is not obviously lower than the initial position. If the pressure decreases, gas leakage occurs. |
|
Monthly |
7 |
Cabinet ground cables |
The ground cables of the lithium battery cabinet are secured to the power distribution ground bar, and the screws are tightened. |
|
Annually |
8 |
Power cables and terminals |
Screws are tightened. The insulation layers of cables are intact and terminals are free from black marks and noticeable sparks. |
|
Annually |
9 |
Battery connection reliability check (recommended) |
|
|
Annually |
No. |
Check Item |
Acceptance Criteria |
Check Method |
Recommended Check Interval |
---|---|---|---|---|
1 |
Battery running status |
The operating status displayed on the SmartLi LCD is charging or discharging, and no fault or alarm information is displayed. |
|
Monthly |
2 |
Indicators on the panel of the BCU |
The green indicator is on, and the yellow (ALARM) and red (FAULT) indicators are off. |
|
Monthly |
3 |
Battery SOC |
Charge the battery continuously for at least one week and record the battery SOC (normally the SOC is 100%). |
|
Monthly |
4 |
Shallow discharge test (recommended) |
During the shallow discharge test, no fault or alarm is displayed on the UPS and SmartLi LCDs. |
|
Quarterly |
5 |
Capacity test (recommended) |
During the capacity test, no fault or alarm is displayed on the UPS and SmartLi LCDs. |
|
Annually |