SmartLi Technical Specifications
Item |
Specifications |
---|---|
Dimensions (H x W x D) |
2000 mm x 600 mm x 850 mm |
Weight |
< 230 kg (excluding battery modules) |
Circuit breaker |
690 V AC/750 V DC, 500 A, 4P |
Fuse |
800 V DC, 315 A (one fuse for each battery string) |
Cabling mode |
Routed in and out from the top |
IP rating |
IP20 |
Item |
Specifications |
---|---|
Operating temperature |
0–40°C CAUTION:
|
Storage temperature |
0–40°C |
Relative humidity |
5%–95% RH (non-condensing) |
Altitude |
0–4000 m (When the altitude ranges from 0 m to 1000 m, the power is not derated. When the altitude exceeds 1000 m, the power is derated as described in IEC 62040-3.) |
Item |
Specifications |
---|---|
CE |
EN 62619, EN 62040-1 |
CB |
IEC 62619, IEC 62040-1 |
Item |
Specifications |
---|---|
Certification standard |
EN/IEC 62040-2 |
Conducted emission (CE) |
EN/IEC 62040-2 |
Radiated emission (RE) |
EN/IEC 62040-2 |
ESD immunity |
IEC 61000-4-2 |
Conducted susceptibility (CS) |
EN/IEC 62040-2 EN/IEC 61000-4-6 |
Radiated susceptibility (RS) |
EN/IEC 62040-2 EN/IEC 61000-4-3 |
Electrical fast transient (EFT) |
EN/IEC 62040-2 IEC 61000-4-4 |
Surge |
EN/IEC 62040-2 IEC 61000-4-5 |
Power magnetic susceptibility |
IEC 61000-4-8 |
Item |
Full-Capacity Cabinet (8+8) |
Half-Capacity Cabinet (8+0) |
Full-Capacity Cabinet (7+7) |
Half-Capacity Cabinet (7+0) |
|
---|---|---|---|---|---|
Number of battery modules |
16 |
8 |
14 |
7 |
|
Rated voltage |
512 V (3.2 V/cell) |
512 V (3.2 V/cell) |
448 V (3.2 V/cell) |
448 V (3.2 V/cell) |
|
Rated capacity |
80 Ah |
40 Ah |
80 Ah |
40 Ah |
|
Energy |
40.96 kWh |
20.48 kWh |
35.84 kWh |
17.92 kWh |
|
Charge voltage |
544 V (3.4 V/cell) |
544 V (3.4 V/cell) |
476 V (3.4 V/cell) |
476 V (3.4 V/cell) |
|
Charge current (The actual maximum charge current depends on the maximum charge capability of the UPS.) |
≤ 80 A (40 A by default) |
≤ 40 A (20 A by default) |
≤ 80 A (40 A by default) |
≤ 40 A (20 A by default) |
|
Maximum discharge current |
500 A |
250 A |
500 A |
250 A |
|
Discharge capacity (Max. operating temperature: 27°C) |
Maximum load power supported by a single cabinet |
230 kW |
115 kW |
200 kW |
100 kW |
Backup time |
10 min |
10 min |
10 min |
10 min |
|
Discharge capacity (Max. operating temperature: 40°C) |
Maximum load power supported by a single cabinet |
200 kW |
100 kW |
- |
- |
Backup time |
10 min |
10 min |
- |
- |
When the UPS5000-E works with the SmartLi, its half-wave loading capacity is 5% of the SmartLi rated capacity (standard configuration).