BCU
The BCU is swappable and supports power conversion, current equalization, and BCU (intra-cabinet BMS) management.
- When the voltages of battery strings are inconsistent, the BCU controls the current balance between battery strings through voltage boosting and balance adjustment to ensure reliable system operation.
- The BCU implements communication inside a SmartLi cabinet and between cabinets, and provides battery management and protection against exceptions.
(1) Output ports |
(2) Input ports |
(3) Positioning lock |
(4) Power switch (POWER ON/OFF) |
(5) Running indicator (NORMAL) |
(6) Alarm indicator (ALM) |
(7) Fault indicator (FAULT) |
(8) Ready switch |
Indicator |
Status |
Description |
---|---|---|
Running indicator (green) |
Steady on |
Discharging state. The SmartLi circuit breaker is switched on. In this case, the UPS can be cold started. |
Blinking intermittently (on for 1s and off for 4s) |
Standby state. The SmartLi circuit breaker cannot be switched on. |
|
Blinking slowly (on for 1s and then off for 1s) |
Charging state. The SmartLi circuit breaker is switched on. In this case, the UPS can be cold started. |
|
Blinking at short intervals (on for 0.25s and then off for 0.25s) |
The power button is pressed down. |
|
Blinking at super short intervals (on for 0.1s and then off for 0.1s) |
Standby state. The SmartLi circuit breaker can be manually switched on. |
|
Off |
Power-off state. |
|
Alarm indicator (yellow) |
Steady on |
A minor alarm is generated. |
Off |
The device is powered off or has no minor alarm. |
|
Fault indicator (red) |
Steady on |
A critical alarm is generated. |
Off |
The device is powered off or has no critical alarm. |