Cables
Cables
When selecting, connecting, and routing cables, follow local safety regulations and rules.
When the external conditions such as cable routing or ambient temperature change, perform verification in accordance with the IEC 60364-5-52 or local regulations.
Table 5-1 SmartLi 2.0 cable list
Cable Name
Recommended Size
Description
Parallel cable
-
Delivered with the SmartLi cabinet. Two types of communications cables are available: 5 m and 15 m. Select one based on the distance between cabinets connected in parallel. A maximum of four 15 m communications cables are supported.
UPS communications cable
-
If the SmartLi is used with the UPS5000-E, UPS5000-S, or UPS5000-H, the cable is delivered with the SmartLi cabinet. You need to crimp RJ45 connectors onto the network cable onsite.
If the SmartLi is used with the integrated UPS in a smart module, the cable is delivered with the system. The cable BOM number is 04071114-001.
Battery module power cable
-
Preinstalled at the bottom of the SmartLi cabinet.
Battery module communications cable
-
Four cables are preinstalled in the SmartLi cabinet, and the others are delivered with battery modules.
Cabinet ground cable
70 mm2
Single-core 90°C flexible power cable with a copper conductor
If multiple cabinets are deployed, ensure that the length and specifications of cables for each cabinet are the same.
DC power cable length: ≤ 50 m
Connector type on the SmartLi cabinet side: DT terminals crimped on cables; bolt specifications: M12x30 mm
DC power cable
120 mm2 (load per cabinet ≤ 150 kW; you are advised to set I1 of the battery circuit breaker to MIN)