Installing DC Power Cables
Single-Cabinet Scenario
If the load of a single battery cabinet is less than or equal to 150 kW, you are advised to set the I1 of the battery circuit breaker to MIN and use cables with a cross-sectional area of 120 mm2. If the load of a single battery cabinet is greater than 150 kW, you are advised to use cables with a cross-sectional area of 150 mm2.
(1) Master SmartLi cabinet |
(1) Master SmartLi cabinet |
Multi-Cabinet Scenario
If the load of a single battery cabinet is less than or equal to 150 kW, you are advised to set the I1 of the battery circuit breaker to MIN and use cables with a cross-sectional area of 120 mm2. If the load of a single battery cabinet is greater than 150 kW, you are advised to use cables with a cross-sectional area of 150 mm2.
(1) Master SmartLi cabinet |
(1) Master SmartLi cabinet |