Checking the Hardware Installation
After installing all devices and cables, check the hardware installation. This helps ensure proper running of devices.
Context
Hardware installation check on the storage system focuses on the cable layout. Table 3-17 provides the cable layout checklist.
No. |
Check Item |
---|---|
1 |
Labels are correctly attached to cables. |
2 |
Cables that pass the cable ladder are secured on the beam of the cable ladder. |
3 |
Cable troughs are used for cables laid outside a bay, and these cables are in the cable troughs. |
4 |
Ground cables of a bay are connected correctly and reliably. |
5 |
Do not tightly bind the external power cables and ground cables. Separately deploy them with at least 150-mm space in between. Also, separately deploy these two types of cables from the signal cables with at least 30-mm in between. |
6 |
Cables are laid out in an untangled and orderly fashion. |
7 |
Cables are bound in a rectangular shape (Single-core cables can be bound in a round shape). |
8 |
Cables are bent at a radius larger than 60 mm. Cable ties are not installed where a cable bends. |
9 |
Cable ties are properly installed at equal spacing and in the same direction. The excess of cable ties is trimmed off without remaining rough edges. |
10 |
Optical fibers do not have unnatural bends and squeezes. |
11 |
The bending radius of optical fibers is equal to or larger than 50 mm. |