Replacing the PID Module
- Open the PID cabinet door and adjust the support bar.Figure 7-12 Adjusting a support bar
- Open the maintenance compartment door of the PID module, and remove the cover from the connection box.Figure 7-13 Removing the cover from a connection box
- Disconnect cables from the faulty PID module, and label the cables.
- Remove the pipe connector from the faulty PID module.
- Remove the faulty PID module.Figure 7-14 Removing a faulty PID module
- Install a new PID module.
- Open the maintenance compartment door of the PID module, and remove the cover from the connection box.
- Connect the removed cables to the new PID module based on the cable labels.
- Secure the pipe connector to the PID module.
- Reinstall the connection box cover and close the maintenance compartment door of the PID module.
- Retract the support bar and close the PID module cabinet door.
After ensuring that the PID module is powered on, set parameters by referring to the SmartLogger3000 User Manual.