2001
|
High String Input Voltage
|
Major
|
The PV array is not properly configured. Excessive PV modules are connected in series to the PV string, and therefore the open-circuit voltage exceeds the maximum SUN2000 operating voltage.
Cause ID = 1, 2 - 1: The PV1 input voltage is high.
- 2: The PV2 input voltage is high.
|
Check the serial connection configuration of the PV string and ensure that the PV string open-circuit voltage is not greater than the maximum operating voltage of the SUN2000. After the PV array configuration is corrected, the alarm disappears.
|
2002
|
DC Arc Fault
|
Major
|
The PV string power cables arc or are in poor contact.
Cause ID = 1, 2
- 1: PV1 DC arc fault
- 2: PV2 DC arc fault
|
Check whether the string cables arc or are in poor contact.
|
2011
|
String Reversed
|
Major
|
The PV string is reversely connected.
Cause ID = 1, 2
- 1: PV1 is reversely connected.
- 2: PV2 is reversely connected.
|
Check whether the PV string is reversely connected to the SUN2000. If yes, wait until the PV string current decreases below 0.5 A, set DC switch to OFF, and adjust the PV string polarity.
|
2021
|
AFCI Check Failure
|
Major
|
The AFCI check fails.
Cause ID = 1, 2
- 1: The AFCI check circuit is abnormal.
- 2: The AFCI circuit is faulty.
|
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the fault persists, contact your dealer or Huawei technical support.
|
2032
|
Grid Failure
|
Major
|
Cause ID = 1
- The power grid experiences an outage.
- The AC circuit is disconnected or the AC circuit breaker is OFF.
|
- Check the AC voltage.
- Check whether the AC circuit is disconnected or the AC circuit breaker is OFF.
|
2033
|
Grid Undervoltage
|
Major
|
Cause ID = 1
The grid voltage is below the lower threshold or the low voltage duration has lasted for more than the value specified by low voltage ride-through (LVRT).
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The SUN2000 automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid voltage is within the allowed range. If no, contact the local power operator. If yes, modify the grid undervoltage protection threshold through the mobile App, SmartLogger, or network management system (NMS) with the consent of the local power operator.
- If the fault persists for a long time, check the connection between the AC switch and the output power cable.
|
2034
|
Grid Overvoltage
|
Major
|
Cause ID = 1
The grid voltage exceeds the higher threshold or the high voltage has lasted for more than the value specified by high voltage ride-through (HVRT).
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The SUN2000 automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid voltage is within the allowed range. If no, contact the local power operator. If yes, modify the grid overvoltage protection threshold through the mobile App, SmartLogger, or NMS with the consent of the local power operator.
- Check whether the peak voltage of the power grid is too high. If the fault persists and cannot be rectified for a long time, contact the power operator.
|
2036
|
Grid Overfrequency
|
Major
|
Cause ID = 1
Power grid exception: The actual power grid frequency is higher than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The SUN2000 automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the allowed range. If no, contact the local power operator. If yes, modify the grid overfrequency protection threshold through the mobile App, SmartLogger, or NMS with the consent of the local power operator.
|
2037
|
Grid Underfrequency
|
Major
|
Cause ID = 1
Power grid exception: The actual power grid frequency is lower than the standard requirement for the local power grid.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The SUN2000 automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the allowed range. If no, contact the local power operator. If yes, modify the grid underfrequency protection threshold through the mobile App, SmartLogger, or NMS with the consent of the local power operator.
|
2038
|
Unstable Grid Frequency
|
Major
|
Cause ID = 1
Power grid exception: The actual grid frequency change rate does not comply with the local power grid standard.
|
- If the alarm occurs occasionally, the power grid may be abnormal temporarily. The SUN2000 automatically recovers after detecting that the power grid becomes normal.
- If the alarm occurs frequently, check whether the power grid frequency is within the allowed range. If no, contact the local power operator.
|
2039
|
Output Overcurrent
|
Major
|
Cause ID = 1
The power grid voltage drops dramatically or the power grid is short-circuited. As a result, the SUN2000 transient output current exceeds the upper threshold and therefore the SUN2000 protection is triggered.
|
- The SUN2000 detects its external working conditions in real time. After the fault is rectified, the SUN2000 automatically recovers.
- If the alarm occurs frequently and affects the energy yield of the power plant, check whether the output is short-circuited. If the fault persists, contact your dealer or Huawei technical support.
|
2040
|
Output DC Component Overhigh
|
Major
|
Cause ID = 1
The DC component of the SUN2000 output current exceeds the specified upper threshold.
|
- The SUN2000 detects its external working conditions in real time. After the fault is rectified, the SUN2000 automatically recovers.
- If the alarm occurs frequently, contact your dealer or Huawei technical support.
|
2051
|
Abnormal Residual Current
|
Major
|
Cause ID = 1
The insulation impedance of the input side to PE decreases when the SUN2000 is operating.
|
- If the alarm occurs occasionally, the external circuit may be abnormal temporarily. The SUN2000 automatically recovers after the fault is rectified.
- If the alarm occurs frequently or persists, check whether the impedance between the PV string and the ground is too low.
|
2062
|
Low Insulation Resistance
|
Major
|
Cause ID = 1
- A short circuit occurs between the PV array and the ground.
- The ambient air of the PV array is damp and the insulation between the PV array and the ground is poor.
|
- Check the output impedance of the PV array to ground. If there is a short circuit or lack of insulation, rectify it.
- Check that the PE cable of the SUN2000 is correctly connected.
- If the impedance is lower than the specified protection threshold in rainy and cloudy days, set Insulation resistance protection using the mobile App, SmartLogger, or NMS.
Current insulation resistance: x MΩ, possible short circuit position: x%. The short circuit position is valid for a single PV string. If there are multiple PV strings, check the PV strings one by one. For details, see Locating Insulation Resistance Faults.
|
2063
|
Overtemperature
|
Minor
|
Cause ID = 1
- The SUN2000 is installed in a place with poor ventilation.
- The ambient temperature is higher than the upper threshold.
- The SUN2000 is not working properly.
|
- Check the ventilation and ambient temperature of the SUN2000 installation position.
- If the ventilation is poor or the ambient temperature exceeds the upper threshold, improve the ventilation and heat dissipation.
- If the ventilation and ambient temperature both meet requirements, contact your dealer or Huawei technical support.
|
2064
|
Device Fault
|
Major
|
An unrecoverable fault has occurred on a circuit inside the SUN2000.
Cause ID = 1–12 - 1: The Boost input is short-circuited.
- 2: The Boost input experiences overcurrent.
- 3: The control circuit is faulty.
- 4: The inverter circuit is abnormal.
- 5: The residual current sensor is faulty.
- 6: The temperature detection fails.
- 7: EEPROM read/write fails.
- 8: The auxiliary power supply is abnormal.
- 9: The grid-tied relay is abnormal.
- 10: The DC bus experiences overvoltage.
- 11: The DC bus experiences undervoltage.
- 12: The DC bus experiences voltage imbalance.
|
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the fault persists, contact your dealer or Huawei technical support.
|
2065
|
Upgrade Failed or Version Mismatch
|
Minor
|
The upgrade does not complete normally.
Cause ID = 1–4, 7 - 1. The software and hardware of the main controller do not match.
- 2: The main and auxiliary controller software versions do not match.
- 3: The monitoring and power controller software versions do not match.
- 4: The upgrade fails.
- 7: The optimizer upgrade fails.
|
- Perform an upgrade again.
- If the upgrade fails for multiple times, contact your dealer or Huawei technical support.
|
61440
|
Monitoring Unit Faulty
|
Minor
|
Cause ID = 1
- The flash memory is insufficient.
- The flash memory has bad sectors.
|
Turn off the AC output switch and DC input switch, and then turn them on after 5 minutes. If the fault persists, replace the monitoring board or contact your dealer Huawei technical support.
|
2067
|
Faulty Power Collector
|
Major
|
Cause ID = 1
The smart power sensor is disconnected.
|
- Check that the configured power meter model is the same as the actual model.
- Check that the communications parameters for the smart power sensors are the same as the SUN2000 RS485 configurations.
- Check whether the smart power sensor is powered on and whether the RS485 communications cable is connected.
|
2068
|
Battery Abnormal
|
Minor
|
The battery is faulty, disconnected, or the battery circuit breaker is OFF when the battery is running.
Cause ID = 1–4 - 1: The battery communication is abnormal.
- 2: The battery port experiences overcurrent.
- 3. The battery enabling cable is not properly connected.
- 4: The battery port voltage is abnormal.
|
- If the battery fault indicator is steady on or blinking, contact the battery supplier.
- Check that the battery enabling/power/communications cable is correctly installed, and that the communications parameters are the same as the SUN2000 RS485 configurations.
- Check that the auxiliary power switch on the battery is set to ON.
- Send a shutdown command on the App. Turn off the AC output switch, DC input switch, and battery switch. Then turn on the battery switch, AC output switch, and DC input switch in sequence after 5 minutes.
- If the fault persists, contact your dealer or Huawei technical support.
|
2070
|
Active Islanding
|
Major
|
Cause ID = 1
When the power grid experiences an AC power outage, the SUN2000 detects islanding proactively.
|
Check that the grid connection voltage of the SUN2000 is normal.
|
2077
|
Off-grid output overload
|
Major
|
Cause ID = 1/2
The output is overloaded or short-circuited.
|
- Check whether the device output is short-circuited.
- Check whether the device load configuration exceeds the rated value.
|
2080
|
Abnormal PV Module Configuration
|
Major
|
PV module configuration does not meet requirements, or the PV module output is reversely connected or short-circuited.
Cause ID = 2, 3, 6, 7, 8, 9
- 2: The PV string power or the number of optimizers connected in series in a PV string exceeds the upper threshold.
- 3: The number of optimizers connected in series in a PV string is less than the lower threshold, the PV string output is reversely connected, or the output of some optimizers in the PV string is reversely connected.
- 6: Under the same MPPT, the number of optimizers connected in series in PV strings connected in parallel is different, or the output of some optimizers in PV strings is reversely connected.
- 7: The optimizer installation position is changed, or PV strings are combined or exchanged.
- 8: The sunlight is weak or changes abnormally.
- 9: In partial configuration scenarios, the PV string voltage exceeds the inverter input voltage specifications.
|
Check whether the total number of PV modules, number of PV modules in a string, and number of PV strings meet requirements and whether the PV module output is reversely connected. - ID2: Check whether the PV string power or the number of PV modules connected in series in the PV string exceeds the upper threshold.
- ID3:
1. Check whether the number of optimizers connected in series in the PV string is below the lower threshold.
2. Check whether the PV string output is reversely connected.
3. Check whether the PV string output is disconnected.
4. Check whether the optimizer output extension cable is correct (positive connector at one end and negative connector at the other).
- ID6:
1. Check whether the number of optimizers connected in series in the PV strings connected in parallel under the same MPPT is the same.
2. Check whether the optimizer output extension cable is correct (positive connector at one end and negative connector at the other).
- ID7: When the sunlight is normal, perform the optimizer search function again.
- ID8: When the sunlight is normal, perform the optimizer search function again.
- ID9: Calculate the PV string voltage based on the number of PV modules in the PV string and check whether the PV string voltage exceeds the upper threshold of the inverter input voltage.
|
2081
|
Optimizer Fault
|
Warning
|
Cause ID = 1
An optimizer is faulty.
|
Go to the optimizer information screen to view the fault details.
|
2082
|
Grid-tied/Off-grid Controller Abnormal
|
Major
|
Cause ID = 1
The inverter fails to communicate with the Smart Backup Box.
Cause ID = 2
An unrecoverable fault occurs on a circuit inside the Smart Backup Box.
|
- Send a shutdown command on the App. Turn off the AC output switch, DC input switch, and battery switch.
- Check whether the power cable and RS485 cable between the Smart Backup Box and the inverter are normal.
- After 5 minutes, turn on the battery switch, AC output side, AC output switch, and DC input switch.
- If the alarm persists, contact your dealer or Huawei technical support.
|