Environment Specifications
Climatic Environment Requirements
Item |
Specifications |
---|---|
Temperature |
|
Humidity (RH, non-condensing) |
|
Altitude |
Operating altitude: ≤ 3000 m (9842.4 ft), 40°C@900 m (104°F@2952.72 ft) NOTE:
When the altitude is above 900 m (2952.76 ft), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft). |
Corrosive gas contaminants |
|
Particulate pollutant |
|
Equipment Room Environment Requirements
Item |
Specifications |
---|---|
Operating temperature |
|
Flow rate |
The cabinet is fully configured with 2288C V5 (CH121L V5): 40 L/min |
Operating pressure |
≤ 3.5 bar |
Inlet-outlet water pressure difference of the full liquid cooling cabinet |
≥80 kPa |
Connectors on the full liquid cooling cabinet |
|
Item |
Specifications |
---|---|
Working medium |
25% glycol and deionized water (with BTA corrosion inhibitor) |
Connector between the CDU and the primary side |
See the CDU manual. |
Connector between the CDU and the secondary side |
See the CDU manual. |
Pipe materials |
|
Pressure-bearing capability |
> 1 MPa |
Water overpressure protection threshold |
6 bar |
Pipe diameter |
Hose and hard pipe: Calculate the diameter based on the site survey, flow rate, and pressure drop. |
Heat Dissipation Environment Requirements
Item |
Specifications |
---|---|
Failure of one fan or fan module |
Meets heat dissipation requirements. |
Maximum supply water temperature of the manifold |
50°C (122°F) NOTICE:
When the 2288C V5 uses the 6290 CPU, only 45°C (113°F) is supported. |
Supply water temperature of the primary side |
The inlet water temperature supported by the primary pipe is 5°C to 32°C (41°F to 89.6°F). In special scenarios, the maximum inlet water temperature supported is 35°C (95°F).
NOTE:
Special scenarios refer to the scenarios with restrictions on device configurations and environment specifications. For details, contact Huawei engineers. |
Water quality of the primary side |
|
Auxiliary equipment of the primary side |
|
Manifold flow requirements |
Number of nodes x Flow of a single node x 1.05 |
Flow requirements for the air/liquid heat exchanger in the cabinet |
≥40LPM |
Maximum pressure difference between supply and return water of the air/liquid heat exchanger in the cabinet |
≥80kPa |
Maximum operating pressure of the liquid pipe of the cabinet |
350kPa |
Cooling PUE |
1.05 |