(Optional) Installing the Power Cable of the Tracking System
Precautions
- A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no less than 800 V, current of 16 A, and protection type of gM needs to be installed between the inverter and the tracker controller for protection.
- The cable between the wiring terminal on the power cable and the switch-disconnector-fuse or fuse-switch-disconnector should be less than or equal to 2.5 m.
- Connect the power cable of the tracking system before the AC output power cable. Otherwise, reworking will be caused.
Cable Specifications
Recommended: dual-layer three-core outdoor copper cable with a conductor cross-sectional area of 10 mm2 and a cable outer diameter of 15–18 mm.
Procedure
- Connect the power cable of the tracking system to the terminal block.Figure 5-7 Cable connection