Environmental Specifications
Environmental Specifications
Table 3-2 Environmental specifications
Category
Specifications
Temperature
Operating temperature: 5°C to 35°C (41°F to 95°F) (ASHRAE Classes A2)
Storage range (within three months): –30°C to +60°C (–22°F to +140°F)
Storage range (within six months): –15°C to +45°C (5°F to 113°F)
Maximum temperature change rate: 20°C/h (36°F/h)
Relative humidity (RH, non-condensing)
Operating range: 10% to 85%
Storage range: 5% to 85%
Maximum change rate: 20%/h
Air volume
650 CFM
Maximum altitude
3050 m (10000 ft.)
NOTE:
ASHRAE 2015 compliant:
ASHRAE Class A1 and A2 compliant: For altitudes above 900 m (2952.72 ft.), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.24 ft.) in altitude.
ASHRAE Class A3 compliant: For altitudes above 900 m (2952.72 ft.), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 175 m (574.15 ft.) in altitude.
ASHRAE Class A4 compliant: For altitudes above 900 m (2952.72 ft.), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 125 m (410.10 ft.) in altitude.
Corrosive gaseous contaminant
Maximum corrosion product thickness growth rate:
Copper corrosion rate test: 300 Å/month (meeting level G1 requirements of the ANSI/ISA-71.04-2013 standard on gaseous corrosion)
Silver corrosion rate test: 200 Å/month
Particle contaminant
The equipment room environment meets the requirements of ISO 14664-1 Class 8.
There is no explosive, conductive, magnetic, or corrosive dust in the equipment room.
NOTE:
It is recommended that the particulate pollutants in the equipment room be monitored by a professional organization.
Acoustic noise
The declared A-weighted sound power levels (LWAd) and declared average bystander position A-weighted sound pressure levels (LpAm) listed are measured at 23°C (73.4°F) in accordance with ISO 7779 (ECMA 74) and declared in accordance with ISO 9296 (ECMA 109).
Operating:
LWAd: 6.66Bels
LpAm: 66.6dBA
NOTE:
Actual sound levels generated during operation vary depending on server configuration, load, and ambient temperature.