How Do I Commission a Component?
Context
- On the diagnostic mode screen, you can turn on or off components, and control their output ratio.
- If you need to manually turn on or off system components in diagnostic mode, ensure that the smart cooling product is started before operation.
- Take commissioning the indoor fan as an example.
Procedure
- Choose .
The screen for entering the diagnostic mode:
- Components are interlocked for protection. Therefore, buttons for enabling or disabling certain components may be gray, indicating that operations on the components are not allowed.
- To ensure system security, a component may not promptly respond to operations performed on this screen.
- To exit the diagnostic mode, tap
on the status bar.
- The system automatically exits diagnostic mode when it reaches the maximum diagnostic mode duration.
- Set Indoor fan to 50%.
For safe system operation, when smart cooling product components are turned on, the following coupling relationships are presented:
- When the electric heater is turned on, the indoor fans will turn on automatically.
- When the electrode humidifier is turned on, the indoor fans and inlet water solenoid valve will start automatically.
- When the input value of the indoor fan is less than the minimum speed, the indoor fan will run at the minimum speed.
- Check that the indoor fans run properly, and no alarm generates.
- Choose
to exit the diagnostic mode. or tap