Operating Environment Specifications
Environmental Specifications
Operating temperature |
4–45°C |
---|---|
Operating humidity |
20%–80% RH |
Storage temperature |
–40°C to +70°C |
Storage humidity |
5%–95% RH (non-condensing) |
Inlet water temperature |
15–20°C |
Altitude |
0–4000 m (derated when the altitude is in the range of 1000–4000 m) |
Temperature adjustment precision |
±1°C |
Humidity adjustment precision |
±5% RH |
External residual pressure |
0–300 Pa |
Installation Requirements
Item |
Specifications |
---|---|
Room door |
Width ≥ 1.3 ma; height ≥ 2.5 m |
Elevator |
Elevator door height ≥ 2.5 m, door width ≥ 1.3 m, and car depth ≥ 2.5 m |
Pipe routing mode |
Top pipe routing |
Maintenance space |
For details, see the equipment room layout requirements. |
Power distribution |
Leakage circuit breakers are not recommended for the main power route. If leakage circuit breakers are required by the customer or by local regulations, use the residual current circuit breaker (RCCB) that is not sensitive to the single-phase DC pulses and transient current pulses. |
a: Applicable to the pallet truck located on the side. If the pallet truck is located on the display module or fan side, the door width must be greater than or equal to 2.5 m. |