Checking the Nitrogen Pressure
Checking the Nitrogen Pressure
Context
The unit has been injected with 0.2–0.6 MPa nitrogen before delivery. Check the nitrogen pressure for nitrogen leaks.
Procedure
Pull out the spring pin and rotate the baffle plate to remove the air filter.
Figure 4-8 Removing the air filter
Take out the desiccant bag.
Check whether the bonnet of the needle valve inside the cabinet is missing.
If it is missing, contact technical support.
You can open or close the exhaust valve using a flat-head insulated torque screwdriver.
If no, rotate the exhaust valve counterclockwise. If gas flows out, the system is normal. If no gas flows out, contact technical support.
Figure 4-9 Exhaust valves
(1) Exhaust valve
Follow-up Procedure
Check that thermal insulation foam is in close contact with the pipes, there is no crack in each cutting position, and the chilled water valve is tightly wrapped by thermal insulation foam.