Main Control Module
Appearance
(1) Running indicator |
(2) Alarm indicator |
(3) FE_1 port |
(4) CAN_IN port |
(5) RS485/12V port |
(6) USB port |
(7) SW button |
(8) FE_2 port |
(9) CAN_OUT port |
(10) COM/FE port |
(11) DP port |
Indicators
Indicator |
Status |
Description |
---|---|---|
Running indicator (RUN) |
Off |
The unit is shut down. |
Blinking green |
The unit is started. |
|
Alarm indicator (ALM) |
Off |
No alarm is generated, or a warning has been generated. |
Steady red |
There is a major or critical alarm. |
Communications Ports
- FE_1 and FE_2 ports: connect FE (MAC_CAN) teamwork communications cables.
- CAN_IN and CAN_OUT ports: connect CAN teamwork and RS485 monitoring cascading communications cables.
- RS485/12V port: connects a temperature and humidity (T/H) sensor.
- COM/FE port: connects a monitoring communications cable.
Appearance |
Pin |
FE_1 and FE_2 Ports |
CAN_IN Port |
CAN_OUT Port |
RS485/12V Port |
COM/FE Port |
---|---|---|---|---|---|---|
PIN1 |
FE TX+ |
RS485-N+ |
RS485-N+_1 |
RS485 HT+ |
FE TX+ |
|
PIN2 |
FE TX– |
RS485-N- |
RS485-N-_1 |
RS485 HT– |
FE TX– |
|
PIN3 |
FE RX+ |
- |
- |
12V |
FE RX+ |
|
PIN4 |
- |
RS485-N+ |
RS485-N+_1 |
RS485 HT+ |
RS485-N+_2 |
|
PIN5 |
- |
RS485-N- |
RS485-N-_1 |
RS485 HT– |
RS485-N-_2 |
|
PIN6 |
FE RX– |
- |
- |
- |
FE RX– |
|
PIN7 |
- |
CANH |
CANH |
- |
- |
|
PIN8 |
- |
CANL |
CANL |
GND |
- |
- USB port: connects a WiFi module or USB flash drive.
This port is protected by a security mechanism.
Appearance |
USB Port |
---|---|
|
- DP port: connects to the display module.
Appearance |
DP Port |
---|---|
Connects to the display module for communication and power supply. |
Button
Appearance |
SW Button |
---|---|
When the smart cooling product is shut down and the admin user has logged in, if you hold down the button for more than 10s, a red frame is added to the button that involves a risky operation on the display module within 5 minutes. You can press and hold down the button for 10s to enter the risky operation screen. Exercise caution because a risky operation may affect system data. |