FE Teamwork + FE Monitoring
- Connect teamwork and monitoring communications cables.
Networking
FE Teamwork
FE Monitoring
Protocol
MAC_CAN
Modbus-TCP/SNMP
Description
A teamwork network supports a maximum of 16 units.
-
- If the Modbus-TCP/SNMP protocol is used, customers can purchase the NetEco (a LAN switch is required) or a third-party NMS as the monitoring system.
- If the number of units in a group is greater than 16, FE teamwork needs to be implemented by group. For example, if the number of units under teamwork is 18, they can be divided into two groups, for example, 9+9, 16+2, or 10+8.
Figure 4-29 Connecting communications cablesIf the length of a network cable in the FE teamwork is greater than or equal to 100 m, use the group-based ring networking mode.
- Connecting units with odd numbers: Connect the FE_1 port of the unit with an odd number to the FE_2 port of the unit with the next odd number.
- Connecting units with even numbers: Connect the FE_2 port of the unit with an even number to the FE_1 port of the unit with the next even number.
- Connect FE_2 of No. 1 unit and FE_1 of No. 2 unit, and connect the remaining FE_1 and FE_2 of the last two units.
Figure 4-30 FE teamwork group-based ring networking (using 13 units as an example)