Display Module
Appearance
The display module provides a 7-inch true-color touchscreen that provides man-machine interfaces for query, setting, management, and maintenance.
(1) Indicator |
(2) I2C/12V (reserved) |
(3) DP (display port) port, connected to the main control module |
(4) SW (reserved) |
Indicator |
Buzzer |
Running Status |
---|---|---|
Green |
No buzzing |
The unit is operating properly, or there is a warning. |
Yellow |
Intermittent buzzing |
There is an unacknowledged major alarm. |
Red |
Constant buzzing |
There is an unacknowledged critical alarm. |
Note: Hold down the SW button on the main control module for about 1s. In all the preceding states, the indicator blinks at 1 Hz (on for 0.5s and off for 0.5s). |
Functions
Function |
Description |
---|---|
Single unit control |
Each unit has an independent control system to ensure normal and high-precision operation. |
Operations |
Users can set parameters and query status on the 7-inch true-color touchscreen. |
Four remote functions |
The module supports the four remote functions when it connects to the NMS.
|
Teamwork |
When multiple units work cooperatively, the controller optimally distributes the heat load to reduce energy consumption and provides backup to improve reliability.
|
Remote management |
Users can remotely manage the operating status of one or more units. |
Storage |
|
Log backtracking |
Access logs can be backtracked. Up to 1000 historical operation logs recording login and setting can be stored. |
Power management |
Supports alarm reporting, fault diagnosis, and alarm recording for reverse phase, open phase, overvoltage, undervoltage, high frequency, and low frequency; provides functions such as automatic protection, recovery, and restart. |
Features
- The display panel provides a touchscreen with a user-friendly interface.
- The controller is highly precise and responsive.
- The display panel is protected by a multi-level password protection mechanism to avoid misoperation.
- The password is verified each time the system is started or shut down to ensure system operation security.
- The controller provides functions such as automatic recovery after power failure and water leakage detection, improving the system reliability.
- The module displays the operating status, time, and other parameters of components in real time.
- Multiple display languages are supported.
- O&M personnel can export fault records in one-click mode, making it easy to operate the device and know the running status of the device.
- The device supports communications protocols such as Modbus RTU, Modbus TCP, and SNMP, facilitating connection to the network management system.
- The display panel intelligently identifies abnormal parameter settings (incorrect commands) and rejects them automatically.