Shutting Down a UPS
Normal Mode
On the default screen, press and hold OFF/ENTER for more than 5s. Release the button when you hear the buzzer buzzing. The UPS inverter is shut down. The UPS transfers to bypass mode when the mains is available.
Battery Mode
In battery mode, press and hold OFF/ENTER for more than 5s. Release the button when you hear the buzzer buzzing. The UPS in battery mode is shut down.
Shutting Down the Inverter to Transfer the UPS to the No Output State
- Shut down loads.
- Perform the shutdown operation on the UPS. The UPS shuts down the inverter and transfers to bypass mode. If mains parameters are inconsistent with bypass parameters, the UPS transfers to standby mode.
- Switch off the AC input circuit breaker Km and output circuit breaker Q for the UPS. After all indicators turn off and fans stop, the UPS shuts down and the loads power off.