Installing Cables for Parallel UPSs
- Before parallel running, ensure that all output circuit breakers for each UPS are ON. Otherwise, a UPS fault (error code #72) will occur.
- Batteries must be connected for parallel running.
This section describes how to install cables for two UPSs and two lithium batteries. The actual situation may vary.
Installing Power Cables
- Switch off the upstream AC circuit breaker for the UPS.
- Remove the AC input, AC output, and battery input terminal cover from each UPS.
- Install AC output power cables, AC input power cables, and then battery input cables in sequence.Figure 3-10 AC input, AC output, and battery input wiring diagram (sharing battery strings)Figure 3-11 AC input, AC output, and battery input wiring diagram (not sharing battery strings)
Installing Battery Cables
After lithium batteries are connected in parallel, connect signal cables to the BMS ports on the UPS. Install a build-out resistor at the COM-OUT port on the last lithium battery.
- UPS sharing battery stringsFigure 3-12 Installing the battery PE cable
(1) Ground bar
Figure 3-13 Installing battery cables (rack-mounted, front view)(1) Busbar
Figure 3-14 Installing battery cables (rack-mounted, rear view)
- UPS not sharing battery stringsFigure 3-15 Installing the battery PE cable
(1) Ground bar
Figure 3-16 Installing battery cables (rack-mounted, front view)(1) UPS rear view
Figure 3-17 Installing battery cables (rack-mounted, rear view)