Parameter Settings
Press and hold SELECT for 1s on a non-setting screen to access the login screen for parameter settings. The initial password is 000001. Enter the correct password to access the UPS setting mode. Press SELECT to select a parameter, and then press OFF/ENTER to confirm the setting.
If you forgot the password, press and hold ON/MUTE, SELECT, and OFF/ENTER at the same time for 3s on the password login screen to reset the password.
If you enter incorrect passwords for multiple times, the password input screen will be locked and you cannot continue to enter the password. The following table lists the detailed data.
Incorrect Password Attempts |
Lockout Duration |
Display |
---|---|---|
3 ≤ Attempts < 5 |
1 minute |
|
5 ≤ Attempts < 10 |
5 minutes (4 minutes and 59 seconds are displayed as 4, and seconds are not displayed.) |
|
10 ≤ Attempts |
60 minutes (59 minutes and 59 seconds are displayed as 59, and seconds are not displayed.) |
Name |
Display |
Description |
---|---|---|
Manual alarm clearance |
DIS: Manual alarm clearance (disabled by default) ENA: Enable manual alarm clearance. Ten seconds after you exit the setting screen, the device restores the initial status of manual alarm clearance and cancels alarms. |
|
Maximum charge current |
|
|
Output voltage |
You need to shut down the inverter before changing the output voltage. 220: indicates that the output voltage is 220 V AC. 230: indicates that the output voltage is 230 V AC (default value). 240: indicates that the output voltage is 240 V AC. |
|
Set the number of parallel UPSs |
|
|
Battery discharge time |
|
|
Battery capacity |
|
|
Output frequency |
You need to shut down the inverter before changing the output frequency.
|
|
ECO mode |
DIS: Disable ECO mode (default). When the mains is available, the UPS works in normal mode. If the mains frequency is unstable, the UPS works in battery mode. ENA: When the mains is available, the UPS works in ECO mode. |
|
Shallow discharge test |
DIS: Disable shallow discharge test (default). ENA: Enable shallow discharge test. The shallow discharge test time is controlled by the battery discharge time and discharge percentage. |
|
Discharge percentage |
|
|
Buzzer off setting |
Enable or disable the buzzer off function. ENA: Enable the buzzer off function. DIS: Disable the buzzer off function (disabled by default) |
|
Automatically return to the default screen |
ENA: Return the default display screen (default). If no button is pressed within 1 minute in any mode, the default screen (input voltage/output voltage) is displayed. DIS: Stay on the current screen. The display will stay on the screen currently turned on by the user. |
|
Equalized charge voltage |
|
|
Float charge voltage |
|
|
Battery (EOD) point |
|
|
Set the communications address |
The default communications address is 001, which is used for the RS485 communications ports (connect to northbound devices). Set different communications addresses for parallel UPSs. |
|
Restore factory settings |
DIS: Disable the function of restoring factory settings (default). ENA: Enable the function of restoring factory settings. The setting takes effect after you exit the setting screen. After factory settings are restored, the output voltage, calibration parameters, and log information are not restored. |
|
LCD password control |
ENA: Enable LCD password control (default). After the function is enabled, a password is required for accessing the settings screen. DIS: Disable LCD password control. After LCD password control is disabled, no password is required for accessing the setting screen. However, other users may have the permission to access the parameter setting screen to modify parameters. |
|
Password setting |
|
|
Altitude-based derating |
|
|
Deep discharge test |
DIS: Disable battery deep discharge test (default). ENA: Enable battery deep discharge test. This function can be enabled only when the battery SOC is 100%. |
|
Battery string sharing |
ENA: Enable battery string sharing (default). DIS: Disable battery string sharing. |
|
Exit the setting mode |
ESC: Exit the setting mode. |