Mains Input Electrical Specifications
Item |
Specifications |
||||
---|---|---|---|---|---|
Rated input voltage |
220 V AC/230 V AC/240 V AC |
||||
Input voltage range |
110–280 V AC (normal startup); linearly derated when the voltage is below 176 V AC; 50% loaded when the voltage is 110 V AC |
||||
Rated input frequency |
50 Hz/60 Hz |
||||
Input frequency range |
50 Hz/60 Hz±4 Hz |
||||
Input power factor |
≥0.98 (100% load); ≥ 0.94 (50% load); ≥ 0.86 (30% load) |
||||
THDi |
< 6% (100% load); < 9% (50% load); < 14% (30% load) |
||||
Voltage detection precision |
2% |
||||
Generator input capacity |
≥ 1.5 times the UPS capacity |
||||
Inrush current |
≤ five times the rated current |
||||
Static withstand voltage |
320 V AC input, no damage to the UPS (at least 2 hours) |