Linkage Control
Prerequisites
- You have obtained the IP address of the ECC800-Pro as well as the user name and password used for WebUI login.
- You have prepared a PC with an IP address in the same network segment as that of the ECC800-Pro, and the PC is connected to the WAN_1 port on the ECC800-Pro.
- Ensure that Enable linkage control function is Yes.
Linkage Grouping
Linkage Category |
Default Status |
Function |
---|---|---|
Link emergency ventilation with clasp lock open |
off |
Set this linkage status to on:
|
Link smoke alarm with clasp lock open |
off |
When this linkage status is set to on:
|
Link fire control with clasp lock open |
off |
When this linkage status is set to on:
|
Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm Is Generated
Procedure
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose .
- Ensure that Enable linkage control function is Yes.
- On the Linkage Group tab page, set Link smoke alarm with clasp lock open to on.
Select Link smoke alarm with clasp lock open under Linkage Group. If its value is on, the corresponding logic configurations under Linkage Logic List are available. If its value is off, the corresponding logic configurations under Linkage Logic List are unavailable.
- Modify the AI/DI_1 signal name.
- Choose Batch Signal Configuration tab page is displayed. . The
- Set Device type to ECC800, set Device name to ECC800, and click OK.
- On the query result tab page, set the new signal name of AI/DI_1 to Smoke and click Submit.
- Enable the AI/DI device.
- Choose .
- Set Smoke sensor to Enable and click Submit.
- Confirm that Smoke sensor type is automatically identified as Smoke sensor or Smoke sensor(NC).
- Click Unhide All Advanced Signals, and click Power Supply Parameters. Ensure that III power supply enable(AIDI_1/DO) is Enable.
Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is Generated
Context
In this example, the fire extinguishing system connects to port AI/DI_3. The actual port prevails.
Procedure
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose .
- Ensure that Enable linkage control function is Yes.
- On the Linkage Group tab page, set Link fire control with clasp lock open to on.
Select Link fire control with clasp lock open under Linkage Group. If its value is on, the corresponding logic configurations under are available. If its value is off, the corresponding logic configurations under are unavailable.
- Modify the AI/DI_3 signal name.
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose Batch Signal Configuration tab page is displayed. . The
- Set Device type to ECC800, set Device name to ECC800, and click OK.
- On the query result tab page, set the new signal name of AI/DI_3 to Fire and click Submit.
- Enable the AI/DI device.
- Choose .
- Set Fire sensor to Enable. Click Submit to access the AI/DI_3 setting page.
- Select Fire sensor type and set it to Normal Open or Normal Close as required.
- Click Unhide All Advanced Signals, and click Power Supply Parameters. Ensure that II power supply enable(AIDI_3/COM2/AIDI_5) is Enable.
- Click Submit.
Link emergency ventilation with clasp lock open
Procedure
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose .
- Ensure that Enable linkage control function is Yes.
- On the Linkage Group tab page, set Link emergency ventilation with clasp lock open to on.
Select Link emergency ventilation with clasp lock open under Linkage Group. If its value is on, the corresponding logic configurations under Linkage Logic List are available. If its value is off, the corresponding logic configurations under Linkage Logic List are unavailable.