Commissioning Sensors
Setting and Adding a Smoke Detector (Connected to an AI/DI Port on the ECC800-Pro)
If a smoke detector is installed, perform the following steps to configure it.
Procedure
- Set smoke detector parameters.
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose Batch Signal Configuration tab page is displayed. . The
- Set Device type to ECC800, set Device name to ECC800, and click OK.
- On the query result tab page, set the new signal name of AI/DI_1 to Smoke and click Submit.
- Choose .
- Set Smoke sensor to Enable and click Submit.
- Check the monitoring functions of smoke detector.Table 5-7 Commissioning the detector
Check Method
Normal Connection Status
Alarm Clearance Method
Simulate a smoky environment under the smoke detector.
Smoke DI alarm is displayed on the active alarm page of the app or WebUI.
Disconnect the smoke detector cable and then reconnect it to clear the alarm.
Commissioning a T/H Sensor
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H sensor, and the other end has been connected to the COM port on the ECC800-Pro.
Procedure
- Set a device address for the T/H sensor.
Operate the DIP switch on the T/H sensor to set the device address for the sensor.
Toggle switches 1 to 6 specify the device address in binary mode. ON indicates 1, and OFF indicates 0.
Figure 5-6 DIP switch definitions for T/H sensorsNumbers 1 and 2 indicate the DIP switch settings of T/H sensors. The DIP switch of the T/H sensor on the front door is set to 2, and that of the T/H sensor on the rear door is set to 1.
Table 5-8 Setting device addressesAddress
Toggle Switch 1
Toggle Switch 2
Toggle Switch 3
Toggle Switch 4
Toggle Switch 5
Toggle Switch 6
1
ON
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
- Add a T/H sensor.
- Check the function of the T/H sensor.Table 5-10 Function check
Check Method
Normal Connection Status
Check the running information about the T/H sensor on the WebUI.
Choose
, and view the current cabinet temperature and humidity.Set T/H sensor alarm thresholds.
Choose High temperature alarm threshold, Low temperature alarm threshold, High humidity alarm threshold, and Low humidity alarm threshold as required.
and setNOTE:The default values of High temperature alarm threshold, Low temperature alarm threshold, High humidity alarm threshold, and Low humidity alarm threshold for the cold aisle are 35.0°C, 5.0°C, 85.0% RH, and 15.0% RH respectively. The default values of High temperature alarm threshold, Low temperature alarm threshold, High humidity alarm threshold, and Low humidity alarm threshold for the hot aisle are 45.0°C, 10.0°C, 85.0% RH, and 15.0% RH, respectively. The cold and hot aisles can be determined based on the DIP switch settings of the T/H sensors.
Commissioning the Electrode Water Sensor
Prerequisites
One end of the network cable has been stripped, core wires 7 and 8 have been connected to the cable delivered with the electrode water sensor, and the other end of the network cable has been connected to the AI/DI port on the rack environment unit.
Context
- To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. The specific alarm then can be reported.
- If the sensor is prefabricated, only check its settings.
- The actual value may vary. Only the method of the parameter settings is described.
Procedure
- Set water sensor parameters.
The following describes how to connect a water sensor to the AI/DI_2 port on the ECC800-Pro.
- Log in to the ECC800-Pro WebUI as an administrator.
- Choose Batch Signal Configuration page is displayed. . The
- Set Device type to ECC800, set Device name to ECC800, and click OK.
- On the query result tab page, set the new signal name of AI/DI_2 to Leak and click Submit.
- Choose .
- Set Leak sensor to Enable and click Submit.
- Set Leak sensor type to Leak sensor(Electroc) and click Submit.
- Click Unhide All Advanced Signals, and click Power Supply Parameters. Ensure that I power supply enable(AIDI_2/COM1/AIDI_4/COM3) is Enable.
- Check functions of water sensors.Table 5-11 Function check
Check Method
Normal Connection Status
Alarm Clearance Method
Immerse the two contacts of the electrode water sensor in water.
Leak DI alarm is generated on the active alarm screen of the app or on the WebUI.
Wipe dry the two contacts of the water sensor. The alarm disappears automatically.