Management System Troubleshooting
Symptom |
Possible Cause |
Measure |
---|---|---|
The Power indicator (green) is off. |
No AC input |
Check whether the AC input is abnormal. |
PSU fault |
Replace the PSU. |
|
The Alarm indicator (yellow) is steady on. |
Overtemperature protection |
|
AC input overvoltage or undervoltage protection |
Check whether the AC input is abnormal. |
|
The Alarm indicator (yellow) is blinking. |
PSU communication failure |
|
Monitoring module communication failure |
||
The Alarm indicator (red) is steady on. |
Output overvoltage protection |
|
No output due to a PSU fault |
Replace the faulty PSU. |
No. |
Symptom |
Possible Cause |
Measure |
---|---|---|---|
1 |
The Run indicator (green) is off. |
There is no AC input. |
If the green indicators on PSUs are steady on, the power input to the system is normal. Otherwise, rectify power grid faults. |
The monitoring module is faulty or not securely installed. |
Reinstall the monitoring module. If the fault persists, replace the monitoring module. |
||
2 |
RJ45 power output indicators turn off (involved ports: AIDI_1 - AIDI_5, COM1-COM4, and DO). |
The corresponding power ports have no output. |
Energize corresponding power ports over the WebUI or network management system. |
The corresponding power ports are short-circuited. |
Check whether the connected load is short-circuited. If yes, eliminate the short circuit. |
||
3 |
The ALM indicator (red) is steady on. |
Faults and alarms are generated. |
View active alarms on the WebUI and clear them one by one. |